LATCHING ALARM EXAMPLES

Example 1

1. Current rises above LL (low-low alarm threshold) — this starts the Latching Alarm

ON timer.

2. Current drops below LL before the Latching Alarm ON time period ends, so

alarming is not enabled. The Latching Alarm ON timer is reset.

3. Current rises above LL — this starts the Latching Alarm ON timer.

4. Current remains above the low-low alarm threshold, beyond the time period

specified by the Latching Alarm ON time setting — this enables the Latching

Alarm (all Latching Alarms for the specific channel are armed).

5. Current rises above H (high alarm threshold) — this starts the high alarm delay

timer.

6. Current rises above HH (high-high alarm threshold) — this starts the high-high

alarm delay timer.

7. Current drops below HH before the high-high alarm delay period ends, so the

high-high alarm delay timer is reset.

8. High alarm is latched at the end of the high alarm delay time period.

Time

HH

H

Amps

L
LL

Latching

alarm ON time

Latching Alarm

OFF Time

L delay

1

3

4

5 6

7

14
12

1.5
0.5

2

LL delay

Time

HH

H

Amps

L
LL

Latching

alarm ON time

Latching

alarm ON time

High-High

alarm delay

High

alarm delay

1

2

3

4

5

6

7

8

14
12

1.5
0.5

Example 2

1. Current rises above LL (low-low alarm threshold) — this starts the Latching Alarm

ON timer.

2. Current remains above the low-low alarm threshold, beyond the time period

specified by the Latching Alarm ON time setting — this enables the Latching
Alarms (all Latching Alarms are armed).

3. Current drops below L (low alarm threshold) — this starts the low alarm delay

timer.

4. Current drops below LL (low-low alarm threshold) — this starts the low-low

alarm delay timer and the Latching Alarm Delay timer.

Note: When the circuit current is continuously below the Low-Low Alarm
Threshold (%) setting for the duration of the Latching Alarm OFF time period
(and longer), the latching alarms for that channel are disarmed. At this point,
the latched alarming feature is disabled (i.e. alarms disarmed), even though
the Low, Low-Low and Latching Alarms are latched.

5. Low alarm is latched at the end of the L delay (low alarm delay) time period.

6. Low-low alarm is latched at the end of the L-L delay (low-low alarm delay) time

period.

7. Current remains below the low-low alarm threshold, beyond the time period

specified in the Latching Alarm OFF time setting, thus setting the Latching Alarm

Off register for that channel