Installing the trip unit bracket and trip unit, Breaker – GE Industrial Solutions ProTrip Conversion Kits AK-15, AK-25, and AKU-25 User Manual

Page 10

Advertising
background image

10

Installing the Trip Unit Bracket and Trip Unit

The ProTrip Trip Unit mounts on the lower right side of
the breaker. The trip unit, mounting plate, support
bracket, and wiring harness are shown in Figure 12.

Figure 12. Trip unit, mounting plate, support bracket, and

harness.

1. For an electrically operated breaker, attach the X

Relay to the inside of the trip unit support bracket
with the three #10 screws and lock washers
provided, as illustrated in Figures 14 and 15. Be sure
to install the insulating shield between the relay and
the support bracket, as shown.

2. Modify the X Relay harness by adding 16-gauge

extension wire, splices, and ring terminals, as
provided. Work one wire at a time. Route the wires
as shown in Figure 5, ensuring that the wires do not
interfere with the closing solenoid plunger or the trip
unit.

3. Mount the support bracket to the two tapped holes on

the right side of the breaker with the screws and lock
washers provided, as in Figure 13 for a manually
operated breaker and in Figure 14 for an electrically
operated breaker.

Figure 13. Trip unit support bracket mounted to the

breaker frame on a manually operated stationary

breaker.

Figure 14. Trip unit support bracket mounted to the

breaker frame on an electrically operated draw-out

breaker.

Advertising