Introduction
Coil Signaling Contacts:

Coil Signaling Contacts indicate the status of the
coil they are installed on. Coil Signaling Contacts
consists of two switches thus enables the status
of the coils thru trip unit and the secondary

disconnect. Status switch thru secondary
disconnect can be power rated or signal rated.
Status switch thru trip unit is a signal rated.

Table 1. Catalog Number and Ratings:


CSC, Power rated Contact:

Cat no

125Vdc 6A

AC Ratings

250Vdc 6A

GCSP1R








DEH-41420 Installation Instructions


EntelliGuard

®

G Circuit Breaker

Accessories


Coil Signaling Contacts



WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.




CSC, Signal rated Contact:

Cat no

AC Ratings 125Vac 0.1A
DC Ratings 30Vdc

0.1A

GCSP2R



Use the following procedure to install Release

Indication Contact accessory into the circuit
breaker.

1. Verify that the rating on the Release Indication
Contact identification plate matches the voltage

rating required for the application, as listed in
Table 1.

2. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows

DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation , et décharger les

resorts d’armement


3. Loosen the 6 screws on front cover (fascia)

using a posidrive screw driver as shown in Fig 1.B