Introduction
Key Interlock Kit:

The breaker key lock is an optional accessory,
which will keep the breaker in trip free state

while

locked.

Maximum 4 keys of Ronis/Profalux or Kirk

type can be used. All EntelliGuard Devices can be

equipped with one of the three locks, that when
fitted as indicated allow the use of one to four key
locks that lock the device in its open position.

Figure 1. (A) Front Cover










Devices are found in two Variants:
1. Factory mounted mechanism:
The breaker/device is supplied off works with all
cams and screws allowing the user to mount a
separately acquired GE type lock kit.

2. Field mountable device:
A kit is supplied allowing the field mounting of the
locking mechanism and allowing the use of a lock
of the correct type purchased elsewhere

Catalog Number:

Catalog No Description
GBKRKR

Kirk Key Interlock kit

GBRONR

Ronis Interlock kit

GBPROR

Profalux Interlock kit


Use the following procedure to install the Key
Interlock Key accessory into the circuit breaker.


1. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF and that the

charge indicator shows DISCHARGE. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.

2. Loosen the 6 screws on front cover (fascia)

using a posidrive screw driver as shown in Fig 1.B

EntelliGuard

®

G Circuit Breaker

Accessories
Key Interlock Kit Breaker Mounted

WARNING: Before installing any accessories, turn
the breaker OFF, disconnect it from all voltage

sources, and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le

déconnecter de toute tension d’alimentation , et

décharger les resorts d’armement

DEH-41407 Installation Instructions

1