Chapter 2. Trip Unit Setup

7

2–7 Ground-Fault Pickup

This function sets the pickup current for ground-fault

protection. The available settings are listed in Table 10 as

multiples of X, the current sensor rating. The maximum

setting may be less than 0.6, depending on the breaker

frame size. Figure 9 illustrates the time-current curve for

ground-fault pickup.

Breaker Frame

Settings as Multiple of X

800–2000 A

.20, .25, .30, .35, .40, .45, .50, .60

3200 A

.20, .22, .24, .26, .28, .30, .34, .37

4000–5000 A

20, .22, .24, .26, .28, .30

Table 10. Settings available for ground-fault pickup according to

breaker frame size.

Figure 9. Time-current curve illustrating ground-fault pickup.

2–8 Ground-Fault Delay

This function sets the delay before the breaker trips when

the ground-fault pickup current is detected. The switch

settings

MIN

,

INT

, and

MAX

correspond to nominal time

delays of .10, .21, and .35 second, respectively. The delay

with

I

2

T OUT

is for the lower limit of each band. The delay

with

I

2

T IN

is at 200% of the pickup setting at the lower

limit of the band.
The

I

2

T OUT

function, illustrated in Figure 10, establishes

a constant time delay.

I

2

T IN

biases the delay with a

constant slope, as shown in Figure 11.

Figure 10. Time-current curve illustrating ground-fault delay with

I

2

T OUT.

Figure 11. Time-current curve illustrating ground-fault delay with

I

2

T IN.

2–9 Defeatable Ground Fault

All rating plugs have the additional setting

OFF

on the

Pickup switch, which defeats ground-fault protection.

These rating plugs are not UL listed.