4–4 trouble-shooting guide – GE Industrial Solutions ProTrip Trip Units for Low-Voltage User Manual

Page 17

Advertising
background image

ProTrip™ Trip Units

Chapter 4. Maintenance and Trouble-Shooting

11

4–4 Trouble-Shooting Guide

The following guide is provided for trouble-shooting and

isolating common problems. It does not cover every

possible condition. Contact the Customer Support Center

at 800-843-3742 if the problem is not resolved by these

procedures.

Symptom

Possible Cause

Corrective Action

1. The health monitor

function of the target

module does not

operate.

Line current is below 20% of

the breaker sensor rating.

The target module is not

seated properly.

At least 20% of the current sensor rating, X, must be

flowing through the breaker to activate this function.

If the load current is below this level, power the Trip

Unit with the Test Kit or the Portable Battery Pack.
Verify that the target module is fully seated in its slot.

2. The trip indication

target will not clear.

The target module batteries

are low.

Replace the batteries in the target module.

3. The battery check

(

BAT

) LED on the

target module does not

light.

The target module batteries

are low.

Replace the batteries in the target module

4. The circuit breaker trips

at too low a current.

The rating plug is not fully

seated.
An incorrect rating plug is

installed.

Verify that the rating plug is fully seated in its slot.

Check the current rating and catalog number of the

rating plug.