Chapter 1. Introduction

1

1–1 Applications

The ProTrip™ Trip Units described in this publication

are used on GE; I-T-E® and ABB®; Allis Chalmers®,

Siemens/Allis®, and Siemens®; and Westinghouse and

Cutler-Hammer® low-voltage power circuit breakers.
Figure 1 shows the ProTrip Trip Unit.

Figure 1. Front view of the ProTrip Trip Unit.

1–2 General

ProTrip Trip Units are the same size and have the same

50-pin male D-sub connector as the RMS9D series of

MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip

Units.
ProTrip Trip Units may be tested with the Trip Unit

installed in the circuit breaker, the rating plug installed in

the Trip Unit, and the breaker carrying current. The Test

Kit plugs into the test socket of the rating plug. The Test

Kit catalog number is TVRMS2 and its operation is

described in GEK–97367.

ProTrip Trip Units are removable from the circuit

breaker. For instructions on installing and removing the

Trip Unit, see Chapter 4.

CAUTION: Removal of a Trip Unit from its breaker must

be performed with the breaker in the

OPEN

or

TRIPPED

position. Draw-out breakers should be racked out first.

ATTENTION: Pour retirer déclencheur, le disjoncteur

doit être en position ouverte ou déclenchée. Les

disjoncteurs débrochables doivent ètre en position

débrochée.

CAUTION: Do not attempt to operate the breaker without

its assigned Trip Unit. Installation of an incorrect Trip

Unit may result in unsafe operation of the breaker.

ATTENTION: Ne pas utiliser le disjoncteur sans son

déclencheur. Une mauvaise installation du déclencheur

peut être dangereuse.

NOTE: Trip Units as received may have settings that are

undesirable for the specific application. Ensure that

settings are appropriately adjusted before energizing.

NOTE: Les disjoncteurs sont livrés avec des réglages

standards qui peuvent être inadéquates pour certaines

applications. Vérifier ces réglages avant de mettre le

disjoncteur sous tension.

1–3 Trip Unit Functions

ProTrip Trip Units have specific standard functions, with

the current rating determined by installation of the rating

plug. The functions of the Trip Unit are as follows:

• Overcurrent protection

– Long-time protection
– Instantaneous protection

• Protection

– Short-time protection, with or without I

2

T

– Ground-fault protection, with or without I

2

T

• Status

– Trip targets
– Health monitor