These instructions apply to the following catalog numbers:

•Circuit breaker modules AMC4GB and AMC6GB
•Circuit breaker frames SGDA, SGHA, SGLA and

SGPA

Installation

1. Prepare the circuit breaker(s).

Before installing the

breakers, install line-end mounting screws into the ON
side of each breaker. Place the breaker vertically on a
flat surface with the ON side up and the OFF side
down, as shown in Figure 1. Install #10-32 pan-head
screws into the ON-side holes on the top of the
breaker. Install #10-32 inserts into the ON-side holes
on the bottom of the breaker. Using two screw drivers,
tighten both the insert and the screw to 20–25 in-lb.

Figure 1. Installing line-end mounting screws in the breaker.

2. Phase balancing for two-pole devices on three-phase

systems.

Reposition the bus clip assembly from A or C

phase to B phase, as shown in Figures 2 and 3.
Remove the screws in the bus clip assembly and move
the bus clip to the B-phase position. Fasten the bus
clip assembly in the new location with the slotted hex-
head SEMS screws provided and tighten to 27–32 in-
lb.

Figure 2. Repositioning the bus clip assembly.

Figure 3. Phase diagram showing locations of bus clips.

GEH5673 Installation Instructions

R03

#10-32

Screw

#10-32

Insert

A & C
Phase

Screws & Bus

Clip Assembly

SEMS

Screws

SEMS

Screws

Screws & Bus

Clip Assembly

B Phase

A & C Phase
As Received

A & B Phase

B & C Phase

Advertising
Table of contents