Car2548dc series dc-dc converters, Data sheet, Alarm table – GE Industrial Solutions CAR2548DC series User Manual

Page 13: Outline drawing

Advertising
background image

GE

Data Sheet

CAR2548DC series dc-dc converters

Input: -36Vdc to -75Vdc; Output: 48Vdc @ 2500W; 3.3Vdc or 5 Vdc @ 1A

December 6, 2013

©2013 General Electric Company. All rights reserved.

Page 13

Alarm Table

Test Condition

LED Indicator

Monitoring Signals

INPUT OK

DC OK

FAULT

FAULT

DC OK

INPUT OK

TEMP OK

1 Normal

Operation

Green

Green

OFF High High High High

2

Low or NO INPUT

OFF

OFF

Red

Low Low Low High

3 OVP

Green

OFF

Red

Low Low High High

4 Over

Current

Green

OFF

Red

Low Low High High

5

Over Temp Alarm

Green

Green

Red

Low High High Low

6

Over Temp Fault

Green

OFF

Red

Low Low High Low

Note: Test condition #2 has 2 modules working in parallel. One module is running and the other has no iNPUT.

Outline Drawing

Input connector: FCI Berg 51939-311 or TYCO 6450129-3

Input mate: FCI Berg 10080594-1E0101LF

10

Output connector: FCI Berg 51939-030
Output mate: FCI Berg 51915-051

10

This is a cable harness with 10 foot of #10ga stranded wire (2 – black and 2 – red) not-terminated on user end

RED LED (FAULT)

Airflow

14.250 ±.020

4.000 ±.020

0.50

0.330

1.610 ±.020

COVER

CHASSIS

POT ADJ.

GREEN LED (DC-OK)

GREEN LED (INPUT-OK)

0.494

1.250

INPUT
CONNECTOR

HANDLE

AIR INLET

#10-32

GROUND STUD

Advertising