5. Wire the circuits. Refer to the label on the circuit

breaker for the proper tightening torque.

6. Filler plate kits. Install filler plate kit AFP6TJS with

AMC2JK and AMC3JK modules. Install filler plate kit

AFP6TJD with AMC4JK and AMC6JK modules.

Procedure for Aluminum Terminations

1. Strip the insulation, being careful to not nick the wire.

2. Clean the wire strands with a wire brush.

3. Thoroughly coat the stripped conductor with a

suitable antioxidant compound, such as ALNOX or

PENETROX A13.

4. Insert the conductor and tighten the connector screw

to the torque indicated on the rating label.