Output, Electrical specifications (continued), Isolation specifications – GE Industrial Solutions ESTW006A0B Series User Manual

Page 3: General specifications

Advertising
background image

Data Sheet
November 5, 2012

ESTW006A0B Series Eighth-Brick Power Modules

36 - 75Vdc Input; 12V/6A

dc

Output

LINEAGE

POWER

3

Electrical Specifications

(continued)

Parameter

Device

Symbol

Min

Typ

Max

Unit

Nominal Output Voltage Set-point

All V

O, set

11.80 12.00 12.24

V

dc

V

IN

= 48V I

O

=I

O, max

, T

A

=25°C)

Output Voltage

All

V

O

11.64

12.36 V

dc

(Overall operating input voltage, resistive load, and
temperature conditions until end of life)

Output Regulation

Line (V

IN

=V

IN, min

to V

IN, max

) All

±0.2 %

V

O, set

Load (I

O

=I

O, min

to I

O, max

)

All

 ±0.2

%

V

O, set

Temperature (T

ref

=T

A, min

to T

A, max

) All

±1.0

% V

O, set

Output Ripple and Noise

(V

IN

=V

IN, min

to V

IN, max

, I

O

= I

O, max

, T

A

=T

A, min

to T

A, max

)

RMS (5Hz to 20MHz bandwidth)

All

25 50 mV

rms

Peak-to-Peak (5Hz to 20MHz bandwidth)

All

75 200

mV

pk-pk

External Capacitance

All

C

O, max

0

2,000

μF

Output Current

All

I

O

0 6 A

dc

Output Current Limit Inception (Hiccup Mode )

All

I

O, lim

6.6 7.8 9.0 A

dc

(V

O

= 90% of V

O, set

)

Output Short-Circuit Current

All I

O, s/c

5 A

rms

(V

O

≤250mV) ( Hiccup Mode )

Efficiency

V

IN

=48V, T

A

=25°C, I

O

=3A,

V

O

= 12V

All

η 90.0 %

V

IN

=48V, T

A

=25°C, I

O

=6A, V

O

= 12V

All

η 90.5 %

Switching Frequency

All

f

sw

280 kHz

Dynamic Load Response

(dI

o

/dt=0.1A/

s; V

IN

= 48V; T

A

=25°C; C

O

>100μF)

Load Change from Io= 50% to 75% or 25% to 50% of
I

o,max

Peak Deviation

All

V

pk

3

% V

O, set

Settling Time (Vo<10% peak deviation)

All t

s

200

s

Isolation Specifications

Parameter

Device

Symbol

Min

Typ

Max

Unit

Isolation Capacitance

All

C

iso

1000

pF

Isolation Resistance

All

R

iso

100

MΩ

I/O Isolation Voltage (100% factory Hi-pot tested)

All

All

2250 V

dc


General Specifications

Parameter

Device

Symbol

Min

Typ

Max

Unit

Calculated Reliability based upon Telcordia SR-332
Issue 2: Method

I

Case 3 (I

O

=80%I

O, max

, T

A

=40°C,

airflow = 200 lfm, 90% confidence)

All FIT

381.7

10

9

/Hours

All MTBF

2,619,994

Hours

Weight (Open Frame)

All

19 (0.7)

g (oz.)

Weight (with Heat Plate)

All

30 (1.1)

g (oz.)

Advertising