Zenith Controls, Inc. ZNET900A, ZNET900B and ZNET901 Operation and Maintenance Manual (18R-1000)

1

Overview and Features

CONTROLS, INC.

R

MONITOR

CONTROL

AUTOMATIC TRANSFER SWITCH

ANNUNCIATOR

POSITION

NORMAL

EMERGENCY

SOURCE

NORMAL

EMERGENCY

TIME DELAY

ACTIVE

BYPASS

TEST

IN PROGRESS

INITIATE

(HOLD UNTIL TRANSFER OCCURS)

1

2

3

4

5

6

7

8

Monitor

LEDs Only

Key

Switch

Control

Enables

Pushbuttons

(Key Removable Only in MONITOR Position)

Green LED ..................... Normal Position

Red LED ........................ Emergency Position

Green LED ..................... Normal Source

Red LED ........................ Emergency Source

Yellow LED .................... Active Time Delay

Black Push Button ........Bypass Time Delay (T or W)

Yellow LED .................... In Progress Test

Black Push Button ........Initiate Test

Customer Field Designation Label

KEY SWITCH —

The MONITOR position allows operation of LEDs only. (Key can be removed in this position) The CONTROL

position allows operation of LEDs and the pushbuttons. (Key cannot be removed in this position)

POSITION — Normal LED (Green)

Indicates that the corresponding Transfer Switch load is connected to the Normal source.

POSITION — Emergency LED (Red)

Indicates that the corresponding Transfer Switch load is connected to the Emergency source.

SOURCE — Normal LED (Green)

Indicates that the corresponding Transfer Switch has an acceptable Normal source.

SOURCE — Emergency LED (Red)

Indicates that the corresponding Transfer Switch has an acceptable Emergency source.

TIME DELAY

Active LED (Yellow)

This flashing LED indicates that the corresponding Transfer Switch has a timer functioning. Timers monitored includes

all timers associated with delaying transfer in either direction. Note: Not available in closed transition mode.

TIME DELAY — Bypass Push Button

Will instantaneously lapse T or W timer whichever is timing concurrent with pushbutton activation. (Key Switch

must be in the Control position) Note: Not available in closed transition mode.

TEST — In Progress LED (Yellow)

Indicates the corresponding Transfer Switch is in a test mode. Indication will occur whether the test is initiated

at the annunciator or locally at the ATS.

TEST — Initiate Push Button

Begins a test sequence (power loss simulation) but must be held until transfer occurs. Transfer is complete

once the Emergency Position and Emergency Source LEDs are both illuminated. Releasing before test

is complete will cancel the test. (Key Switch must be in the Control position)