User settings, Dip switch designations – GE Industrial Solutions ZNET901 User Manual

Page 8

Advertising
background image

DIP Switch Designations

(cont’d)

User Settings

(cont’d)

0

SW8

OFF

SW7

OFF

SW6

OFF

1

ON

OFF

OFF

2

OFF

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

SW5

OFF

OFF

OFF

OFF

OFF

OFF

OFF

SW4

OFF

OFF

OFF

3

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

8

OFF

OFF

OFF

ON

OFF

9

ON

OFF

OFF

ON

OFF

10

OFF

ON

OFF

ON

OFF

11

ON

ON

OFF

ON

OFF

12

OFF

OFF

ON

ON

OFF

13

ON

OFF

ON

ON

OFF

14

OFF

ON

ON

ON

OFF

15

ON

ON

ON

ON

OFF

16

OFF

OFF

OFF

OFF

ON

17

ON

OFF

OFF

OFF

ON

18

OFF

ON

OFF

OFF

ON

19

ON

ON

OFF

OFF

ON

20

OFF

OFF

ON

OFF

ON

21

ON

OFF

ON

OFF

ON

22

OFF

ON

ON

OFF

ON

23

ON

ON

ON

OFF

ON

24

OFF

OFF

OFF

ON

ON

25

ON

OFF

OFF

ON

ON

26

OFF

ON

OFF

ON

ON

27

ON

ON

OFF

ON

ON

28

OFF

OFF

ON

ON

ON

29

ON

OFF

ON

ON

ON

30

OFF

ON

ON

ON

ON

31

ON

ON

ON

ON

ON

The setting of the switches 8 thru

4 for different values shown on

the right:

4. Set switches 8 thru 4 OFF

and 3 thru 1 ON. Press

the service switch. The

entered values are loaded

into the real-time clock/

calendar. The printer will

print the message “End

clock/calendar set.”

5. Restore DIP switches

to the original settings

recorded in the first step.

NOTE:

The DIP switches (switch 4

through switch 8) are also used

to set the annunciator ID which

printed out in the event log in

all the messages. The ID values

(0 through 31) are set as indicated

in the table on the right. The ID

value is read only upon power up

of the unit and therefore changing

the DIP switch settings during

the clock/calendar setting does not

affect the ID number. However,

the switches should be returned

to their original settings after com-

pleting the clock/calendar set pro-

cedure so that the original ID set-

ting is not affected.

6

ZNET900A, ZNET900B and ZNET901 Operation and Maintenance Manual (18R-1000)

Zenith Controls, Inc.

Advertising