Power break, Circuit breakers chapter 3. accessories – GE Industrial Solutions Power Break I 800-2000 Frames 240-600 VAC User Manual

Page 17

Advertising
background image

Power Break

®

Circuit Breakers

Chapter 3. Accessories

11

Figure 18. 1600–2000 A frame electrically operated breaker.

Figure 19. 1600–2000 A frame electrically operated breaker with the

outer cover removed.

Breaker Cover Reassembly

Manually Operated Breakers

1

1

1

1.... Verify that all connections are secure and the breaker

is free of debris.

2

2

2

2.... Verify that the breaker is

off

.

C

C

C

CA

A

A

AU

U

U

UT

T

T

TIIIIO

O

O

ON

N

N

N:::: Verify that the accessory mounting plate

insulator, shown in Figure 20, is properly located so it
will not be damaged when the cover is replaced. The
cover phase barrier must pass to the right side of this
insulator.

3

3

3

3.... Position the charging handle at the home position (6

o’clock) on the cover. Align the cover mounting
screw holes with the breaker base and install the four
cover screws. Tighten the screws to 50–60 in-lbs.

Figure 20. Wire ties on the accessory leads and mounting plate

insulator.

Electrically Operated Breakers

1

1

1

1.... Verify that all connections are secure and the breaker

is free of debris.

C

C

C

CA

A

A

AU

U

U

UT

T

T

TIIIIO

O

O

ON

N

N

N:::: Verify that the accessory mounting plate

insulator is properly located, as shown in Figure 26.

2

2

2

2.... Slide the inner cover assembly onto the breaker base.

Ensure that the crossbar hook engages the drive stud,
as shown in Figure 21.

Figure 21. Crossbar hook engaging the drive hook.

3

3

3

3.... Tighten the inner cover lock screw, shown in Figure

19, to 10 in-lbs.

4

4

4

4.... On 1600–2000 A frame breakers only, replace the two

inner cover mounting screws and tighten to 50–60 in-
lbs.