Power break, Circuit breakers chapter 3. accessories – GE Industrial Solutions Power Break I 800-2000 Frames 240-600 VAC User Manual

Page 23

Advertising
background image

Power Break

®

Circuit Breakers

Chapter 3. Accessories

17

Figure 37. Auxiliary switch wiring diagram.

Catalog

Number

Number of

Switch Elements

Maximum

Current Rating

TPAS2ABx

1–12

6 A at 240 Vac

.25 A at 250 Vdc

.50 A at 125 Vdc

*

Replace x with a number from 1–12 for

the number of switch elements.

Table 7. Auxiliary switch electrical characteristics.

Auxiliary Switch Installation

1

1

1

1.... Remove the circuit breaker cover(s) as described in

Breaker Cover Removal.

• If the breaker was supplied with an L-shaped

bracket (see

Mounting Plate Removal), remove

the two retaining screws, discard the bracket, and
install the mounting plate provided in the kit (see
Mounting Plate Installation).

2

2

2

2.... Both the left and right breaker poles can accept up to

six auxiliary switches. If the left pole contains a shunt
trip, two of the six auxiliary switch positions must be
used for the cut-out switches; thus, only four auxil-
iary switches may be used in the left pole.

3

3

3

3.... If auxiliary switches are to be installed in the right

pole, remove the trip unit by depressing the lock
release lever while lifting up on the trip unit. Remove
the trip unit mounting plate, shown in Figure 38.

4

4

4

4.... Position the auxiliary switch assembly so that the

tapped mounting holes on its bracket line up with
the through holes in the arm stop, as shown in
Figure 39.

5

5

5

5.... Secure the auxiliary switch assembly to the arm stop

with two #8

×

9

/

16

screws and lock washers, as shown

in Figure 40. Tighten the screws to 23 in-lbs.

Figure 38. Trip unit removed from the breaker.

Figure 39. Installing the auxiliary switch assembly.

Figure 40. Securing the auxiliary switch assembly.

6

6

6

6.... Remove knockouts in the side of the base, as

required. Each knockout will accommodate up to
three bundles of wire. Remove all sharp edges with a
file.

7

7

7

7.... Use the supplied wire ties to secure the leads as

shown in Figure 20.

8

8

8

8.... Replace the trip unit mounting plate and trip unit.

9

9

9

9.... Replace the breaker cover(s) as described in Circuit

Breaker Cover Reassembly.

1

1

1

10

0

0

0.... Perform the following functional checks:

a

a

a

a.... With the breaker

off

, use a continuity tester to

verify continuity between the white and brown-

Advertising