Specifications – McDonnell & Miller MM 286 Series 1575 Low Water Cut-Off User Manual

Page 3

Advertising
background image

3

SPECIFICATIONS

M a x i mum Pressure: 150 psi (10.5 kg/cm

2

)

Burner Delay (DOB): 0 to 60 seconds (Field Adjustabl e )

Ambient Te m p : 120˚F Max.

N OT E : The circuit board is protected with a sensor which will
shut down the unit if the temperature at the board ex c e e d s
176˚F (80˚C). The board will reset when the temperature at
the board drops below 167˚F (75˚C).

ELECTRICAL RATINGS & SWITCH RATINGS

Supply

Probe

Full Load (Amps)

Locked Rotor (Amps)

Pilot Duty (VA)

Motor (HP)

Voltage

Voltage

NO (NC), VAC

NO (NC), VAC

NO (NC), VAC

NO (NC), VAC

120 VAC

5 VAC

16 (5.8), 120

96 (34.8), 120

470 (290), 120

1

(1/4), 120

50/60 HZ

maximum

8

(2.9), 240

48 (17.4), 240

470 (290), 240

1

(1/4), 240

M a x i mum System Water Te m p e r a t u r e : 406˚F (208˚C)
M a x i mum System Water Pressure: 250 psi (17.6 kg/cm

2

)

M a x i mum System Steam Pressure: 250 psi (17.6 kg/cm

2

)

All probes in the Series 1575 units are sent from the factory pre-cut to
9" length (229mm). Any of the probes can be used as the low water
cut-off level probe. The 9" length positions the probe at the low water
cut-off cast-in line on the chamber body. The remaining probes can be
‘cut to length’ using a metal cutting saw to achieve desired pump control
(pump on/pump off) and pump differential levels. Approximately 1 inch
of the metal probe rod should be exposed below the Teflon® coating.

Advertising