Circuit Board Layout

STEP 2 - Electrical Wiring

• To prevent electrical shock , turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls installed on the

boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving
the site.

• Boiler manufacturer schematics should always be followed. In the event that the boiler manufacturer’s

schematic does not exist, or is not available from the boiler manufacturer, refer to the schematics provided
in this document.

Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in
property damage, personal injury or death.

WARNING

C over Removal and Installation Pro c e d u r e

a . To remove cove r, use a flathead screw d ri ver to

loosen screws and remove the cover (K).

b . To reconnect cove r, slide over bra ckets and tighten

s c r ews using a flathead screw d ri ve r.

c . Following the appropriate wiring diagram (refer to

page 7) based on your application requirements,
and using BX armored cable or Thinwall electrical
metal tubing connector fittings, make electrical
connections to the junction box (L).

I M P O RTA N T: There must be a minimum space
of

2" (13mm) between connector fittings and

electrical live metal parts.