Dual pump control, Motorized valve and low water cut-off – McDonnell & Miller MM 286 Series 1575 Low Water Cut-Off User Manual

Page 7

Advertising
background image

7

• Connect wire “ a ” from power supply to

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to

t e rminal “ N ” .

• Connect wire “ c ” from pump control circuit

to terminal “ P N O ” .

• Connect wire “ d ” from pump control circuit

to terminal “ P C O M ” .

• Connect wire “ e ” from bu rner control

circuit to terminal “ B N O ” .

• Connect wire “ f” from alarm control circuit

to terminal “ B N C ” .

• Connect wire “ g ” from bu rner or alarm

control circuit to terminal “ B C O M ” .

WIRING DIAGRAMS
Low Water Cut-Off, Alarm and Pump Up Control

• Connect wire “ a ” from power supply to

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to

t e rminal “ N ” .

• Connect wire “ c ” from pump #1 control

circuit to terminal “ P N O ” .

• Connect wire “ d ” from pump #1 control

circuit to terminal “ P C O M ” .

• Connect wire “ e ” from pump #2 control

circuit to terminal “ B N C ” .

• Connect wire “ f” from pump #2 control

circuit to terminal “ B C O M ” .

Dual Pump Control

• Connect wire “ a ” from power supply to

t e rminal “ H ” .

• Connect wire “ b ” from neutral supply to

t e rminal “ N ” .

• Connect wire “ c ” from va l ve control circuit

to terminal “ P N O ” .

• Connect wire “ d ” from va l ve control circuit

to terminal “ P C O M ” .

• Connect wire “ e ” from bu rner control

circuit to terminal “ B N O ” .

• Connect wire “ f” from alarm control circuit

to terminal “ B N C ” .

• Connect wire “ g ” from bu rner or alarm

control circuit to terminal “ B C O M ” .

Motorized Valve and Low Water Cut-Off