EX101/201 INSTALLATION

Fitting Installation.

EX101/201adapters mate with a 1-1/2” female

NPT pipe thread adapter fitting. Any fitting that provides the matching
NPT female thread may be used. Installation procedure compensates
for fitting height differences. Cut a minimum 1-3/4” hole in the pipe. If
possible, measure the wall thickness and write it down for use in depth
setting. Then install the threaded fitting (saddle, weldolet, etc.) on the
pipe.

Meter Installation.

Loosen the compression nut so that the adapter

slides freely. Pull the meter fully upward and finger-tighten the compres-
sion nut. Using a thread sealant, install the adapter in the pipe fitting.
Do not overtighten. Now loosen the compression nut, lower the meter
to the appropriate depth setting (see diagram and instructions that fol-
low). Be sure flow is in the direction of the arrow on the housing. Tighten
compression nut fully.

EX115/215 INSTALLATION

‘Hot tap’ EX meters are designed so they can be installed and serviced
without depressurizing the pipe.

Fitting Installation.

The EX115 and 215 adapters mate with a 2” FNPT

threaded fitting for compatibility with the 2” isolation valve. Any fitting
that provides matching NPT female thread may be used. The installation
procedure compensates for differences in fitting height.

If initial installation is performed on an unpressurized pipe, cut a
minimum 1-3/4” hole in the pipe. If possible, measure the wall thickness
and write it down for use in depth setting. Then install the threaded fitting
(saddle, weldolet, etc.) on the pipe.

If it is necessary to do the initial installation under pressure, any standard
hot tap drilling machine with 2” NPT adapter, such as a Transmate or a
Mueller, can be used. Ordinarily, it is not necessary to use an installation
tool, due to the small diameter tube the meter can be installed by hand
at all but the highest pressures.

Meter Installation.

Remove the sensor unit from the valve assembly.

Using a thread sealant, install the valve assembly on the pipe fitting. If
the initial installation is a pressure (“hot”) tap, remove the 1-1/2” x 2”
adapter bushing at the back of the valve. Thread the tapping machine
on, open the valve, and tap using a minimum of 1-3/4” or maximum
1-7/8” cutter. After retracting the machine and closing the valve, reinstall
the flow sensor. When the sensor is secure, open the valve and adjust
depth setting (see diagram and instructions that follow). Be sure flow is
in the direction of the arrow on the housing. Tighten locking collar and
compression nut fully.

Compression nut

Adapter mates

with

FNPT

threads

Compression nut

2” adapter removes

to mount hot-tap

machine

Full-port 2” ball

valve allows sensor

removal

Mates with 2”

FNPT threads

EX115/215 Sensor

Removal

INSTALLATION