Bell & Gossett V1000187C Circuit Setter Plus Calibrated Balance Valves – Lead-Free User Manual

Page 2

Advertising
background image

Operational Limits

Description

Bell & Gossett Circuit Setter Plus Balance Valves are precision engineered valves used in heating and cooling systems

which function as precise system balancing valves and highly accurate variable orifice flow meters.

Installation Instructions

Circuit Setter Balance Valves are bi-directional valves and can be installed in most attitudes; however, they should be

installed in a position to facilitate the ease of balancing the system.

NPT and sweat style Circuit Setter Balance Valves are equipped with 1/4” NPT plugged drain port. If the drain port is to

be used to drain a riser on the downstream side of a terminal unit, it should be situated on the terminal unit side of the

riser when installing the Circuit Setter.

To retain calibrated accuracy, a minimum length of unrestricted straight pipe adjacent to the valve should be

maintained as follows:

Valve

Temperature

Max Working Pressure

Circuit Setter

NPT

-4°F (-20°C) to 250°F (120°C)

400 PSI (2758 kPa)

Sweat Based on Solder Type

ASTM Std. B16.18

Type Solder

Maximum Limitations 1/2” - 1”

Maximum Limitations 1-1/4” - 2”

Pressure PSI (kPa)

Temp °F (°C)

Pressure PSI (kPa)

Temp °F (°C)

300 (2069)

200 (93)

300 (2069)

175 (79)

250 (1724)

225 (107)

250 (1724)

200 (93)

200 (1379)

250 (121)

175 (1207)

250 (121)

95-5
Tin-Antimony

NOTICE: Bell & Gossett Circuit Setter Balance Valves are not recommended for use with meter connections pointing

down. Dirt and debris will collect in the connections and foul up the readout valves and readout meters.

A

B

Size

Upstream ”A”

(In pipe diameter)

Downstream ”B”

(In pipe diameter)

1/2” - 3”

3

1

When installing the Circuit Setter in a coil hook-up kit, the valve should be installed on the return side of the coil with

union end adapter on the upstream side and other end on the downstream side, except when used on the bypass line.

Be aware of water weight in the valve and connected piping when installing your system.

NOTICE: Never use the valve itself as a form of piping support. Please support valves and piping according to the lo-

cal building code. Failure to follow these instructions may result in property damage.

Circuit Setter Balance Valves With Sweat Connections

1. Use a torch with a sharp pointed flame.

2. Clean tube ends and Circuit Setter connections thoroughly.
3. Use 95-5 (Tin-Antimony) solder and a good grade of flux.