DESCRIPTION

Low Flow Y-strainer Valves are made of brass construction

with an integrated ball valve and strainer.

INSTALLATION INSTRUCTIONS

Model UBYL Low Flow Y-strainer Valves are uni-directional

valves and should be mounted in the supply pipe. Be

sure to install the Model UBYL Low Flow Y-strainer valve

with the arrow pointing in the direction of flow and the

strainer chamber down to prevent air binding and to al-

low materials to collect in the strainer. Be sure to provide

enough space around the valve to remove the strainer

from the valve body for cleaning.

LOW FLOW MODEL UBYL Y-STRAINER VALVES

WITH SWEAT CONNECTIONS

For installing sweat connections:

a) Clean tube ends and valve connections thoroughly per

good piping practices with a fine grade emery cloth or

fine grit sandpaper.

b) For soldering, use 95-5 (Tin-Antimony) solder and a

good grade of flux.

c) Use a torch with a sharp pointed flame.

d) When sweating the joints, adjust the valve to the full

open position, then wrap the valve with a cool wet rag

and then direct the flame with care to avoid subjecting

the valve to excessive heat. Allow the valve to cool before

touching or operating.

e) Check the soldered connection for leaks.

WARNING: Use of improper procedures to

sweat valve model with union

connection into system can damage valve.

Before installing sweat union connection

to valve, remove the union nut and O-ring from the

valve body, then union tailpiece with union nut must

be sweated (soldered) into place. Failure to follow this

instruction could result in property damage and/or

moderate personal injury.

CAUTION: Heat associated with the use of

silver solder may damage valve components

and void the product warranty. Do not use

silver solder. Failure to follow these

CAUTION: Excessive use of solder or flux

may result in damage to the shutoff valve

seat and ball. Do not use excessive solder or

flux. Failure to follow these instructions

LOW FLOW MODEL UBYL Y-STRAINER VALVES

WITH NPT CONNECTIONS

Apply pipe compound conservatively to male connecting

fittings only. After installation, check all joints for

leakage and re-tighten if necessary.

CAUTION: The use of PTFE impregnated

pipe compound and PTFE tape on pipe

threads provides lubricity. Care should be

taken to prevent over tightening

instructions could result in property damage and/or

moderate personal injury.

can result in moderate personal injury and/or property

damage.

which may damage the valve body. Failure to follow

these instructions can result in personal injury and/or

property damage.

OPERATION INSTRUCTIONS

HOW TO USE BELL & GOSSETT LOW FLOW

MODEL UBYL Y-STRAINER VALVES

Y-strainer can be used to isolate hydronic equipment for

repairs and/or to drain the system. To close the Y-strainer

ball valve, move the handle a quarter of a turn until the

handle is perpendicular to the valve and piping.

CAUTION: Hot un-insulated surfaces can

cause burns to the skin. Do not touch hot

surfaces. Failure to follow these instructions

could result in personal injury.

Advertising