Periodically inspect the Low Flow Model UBYL Y-Strainer

Valve for signs of leakage or corrosion. Replace valve cap

o-ring (V57754), if necessary.

WARNING: Corrosion or leakage are

indications that the Low Flow Model UBYL

Y-Strainer Valve must be replaced. Failure to

follow these instructions could result in

serious personal injury or death and property damage.

Due to the different types of material used, the Low Flow

Model UBYL Y-Strainer Valve must be disassembled prior

to disposal. Special handling of certain valve components

may be required by law or may be sensible from an

ecological point of view.

INSULATION

Bell & Gossett recommends that insulation be attached

to Model UBYL Y-Strainer Combination Valve after the

system has been balanced.

NOTE: Tape or other acceptable means should be used to

secure the insulation to the Model UBYL Y-Strainer

Combination Valve.

Patent Pending

CAUTION: Make sure Valve Cap is properly

assembled. Failure to follow these

instructions can result in personal injury
and/or property damage.

Remove the brass cap and drain valve on the Y-strainer.

Grab and remove the strainer. Clean the strainer in water

to remove collected dirt and debris. Check to make sure

that no other debris remains in the valve. Reinstall the

strainer and the valve cap with drain valve. Return

isolation valves to the open position. Pressurize the

system and vent any trapped air at the return side of the

system. Check for strainer cap leaks. If noted, slightly

tighten cap until leakage stops. Replace with a new

strainer (V58577) if necessary.