Bell & Gossett V59075B Low Flow Model UBYL Y-Strainer Combination Valve User Manual

Page 3

Advertising
background image

Read the differential pressure from the coil inlet

isolation valve (typically a strainer) to coil outlet

isolation valve (typically a flow limiting balancing valve).

The differential value minus the pressure drops across the

coil and installed control valves should be less than 60 psi

for proper flow control.

WARNING: Hot water leakage can occur

from readout valves (P/T ports) during probe

insertion and during hookup of readout kit.

Follow the instruction manuals supplied

If Y-strainer pressure drop becomes excessive,

accumulated dirt and contaminants should be blown

through the blow-down line (if installed) to a drain. If a

blow-down line is not installed, see the service

instructions for removing and cleaning the strainer. The

Y-strainers have construction with an integrated ball valve

and will function as a service valve.

SERVICE INSTRUCTIONS

If excessive pressure drop is noted across the Y-Strainer,

the internal strainer has most likely collected a lot of dirt

or debris and needs to be cleaned. Install blow-down line

(hose) to the drain valve on the strainer chamber then

open the drain valve. If flushing the strainer at this point

has not solved the pressure drop problem, the Y-strainer

must be disassembled and strainer to be cleaned.

To clean the strainer, isolate the Y-Strainer from the

system with the integral ball valve on the upstream side

of the strainer. Use an isolation valve downstream of the

strainer and coil to further isolate the system. Allow the

system to cool to 100°F (38°C) or less before handling.

Proceed to drain the isolated system through the drain

valve in the Y-Strainer.

WARNING: Corrosion or leakage are

indications that the Low Flow Model UBYL

Y-Strainer Valve must be replaced. Failure to

follow these instructions could result in

serious personal injury or death and property damage.

Before system start up, flush the hydronic system as part

of commissioning. Make sure the valve cap and drain is

tightened properly. Start the system and inspect the Low

Flow Model UBYL Y-strainer valve for leakage.

HOW TO USE PRESSURE TAPS (P/T PORTS) TO MEASURE

SYSTEM OPERATING CONDITIONS

Using Bell & Gossett Model RP-250B, readout probes,

attach Bell & Gossett differential pressure readout kit to

the readout valves (P/T ports) on the Low Flow Model
UBYL Y-Strainer Valves.

with readout probes and readout kits for safe use.

Failure to follow these instructions could result in

serious personal injury or death and property damage.

Installed P/T Port

Isolation Valve

Strainer