West Control Solutions MRC 5000 Controller Manual User Manual

Page 19

Advertising
background image

19

These parameters apply to each pen, assuming pen 2 is present, and are configured in each respective section.

PARAMETER

PARAMETER

DEFAULT

CODE

DESCRIPTION

SETTINGS OR RANGE

SETTING

InPS

Input Selection

0 - 18

1

0 = J T/C 0 to 760

°

C

1 = J T/C 0 to 1400

°

F

2 = K T/C 0 to 1360

°

C

3 = K T/C 0 to 2500

°

F

4 = T T/C -200 to 400

°

C

5 = T T/C -330 to 750

°

F

6 = R T/C 200 to 1650

°

C

7 = R T/C 400 to 3000

°

F

8 = S T/C 200 to 1650

°

C

9 = S T/C 400 to 3000

°

F

10 = RTD 100 ohm -140 to 400

°

C

11 = RTD 100 ohm -200 to 750

°

F

12 = 0-20mA
13 = 4-20mA
14 = 0-50mV
15 = 10-50mV
16 = 0-25mV
17 = 0-5VDC
18 = 1-5VDC

ICor

Input Correction

-999 to 999*

0

(calibrates sensor to
recorder)

A1

Output Type

OFF = none

OFF

(will show only if present)

Hi = High Alarm
Lo = Low Alarm
HL = High Limit
LL = Low Limit
CH= Control Heat
CC= Control Cool

A2

Output Type

OFF = none

OFF

(will show only if present)

Hi = High Alarm
Lo = Low Alarm
HL = High Limit
LL = Low Limit
CH= Control Heat
CC= Control Cool

dISP

Display Input/Pen Value

On = Display value

On

during normal operation,

OFF = Do not display value

RUN mode

dPOS

Decimal Point Position

0 = nnnn

0

1 = nnn.n
2 = nn.nn

EUU

Engineering Units that

-9999 to 9999*

5000

equate to upper
transducer input
(will show only for Volt
or Milliamp Input types)

EUL

Engineering Units that

-9999 to 9999*

0

equate to lower
transducer input
(will show only for Volt
or Milliamp Input types)