Transmitter power supply, Construction, Evironmental and operating conditions – West Control Solutions MRC 5000 Controller Manual User Manual

Page 28: Digital communicatons, General reference data, Approvals and compliance

Advertising
background image

28

TRANSMITTER POWER SUPPLY

Transmitter Power Supply

Provides up to 40mA of current at 24VDC

CONSTRUCTION

Enclosure

Injection molded Noryl case and cover with acrylic window

NEMA Rating

NEMA 3 standard, NEMA 4X future option

Conduit Openings

Three openings on the right side

Mounting

Panel or wall

Overall Dimensions

14" wide X 14" high X 3.8" deep.
(355.6mm X 355.6mm X 96.5mm)

Panel Cutout

12.7" wide X 12.7" high
(322.58mm X 322.58mm)

Panel Depth

2.5" (63.5mm)

Panel Protrusion

1.3" (33.0mm)

Weight

7 lbs maximum

Retrofit

With adaptor plate, will fit Partlow MRC 7000/ARC 4100 cutout

EVIRONMENTAL AND OPERATING CONDITIONS

Operating Temperature

0

°

C to 55

°

C (32

°

F to 122

°

F)

Storage Temperature

-40

°

C to 65

°

C (-4

°

F to 149

°

F)

Humidity

10 to 90% RH, non-condensing

Vibration

0.3 to 100 Hz @ 0.2g

Mounting Position

Up to 30

°

forward or backward tilt from vertical

Up to 10

°

side tilt from vertical

DIGITAL COMMUNICATONS

Configuration Port

TTL levels

Communications Port

RS-485 serial communications, Half-duplex

Protocol

MODBUS RTU

Bit Rate

9600 bits per second

Parity

Odd

Address

User configurable - 0 to 247

GENERAL REFERENCE DATA

Data Backup

EEPROM for configuration parameters and calibration data
EEPROM for alarm setpoints

Warranty

Two years

APPROVALS AND COMPLIANCE

Safety

UL Approved for USA - UL 1092, UL 916, and QUXY - File E67237
UL Certified for Canada - CSA Spec 142 - File E67237
CE - Complies with EN 61010-1:1993: Pending

Immunity/Susceptability

CE - Complies with EN50082-1992: Pending

Emissions

CE - Complies with EN50081-1: 1992 and EN50081-2:1994: Pending

Limit Device

FM: Pending

Advertising