Chimney connection, Draft hood installation, Vent pipe size – John Wood Atmospheric Gas (Standard) User Manual

Page 13: Vent connectors

Advertising
background image

13

location. A single wall metal vent connector cannot pass

through any interior wall.
When installing a vent connector, please note the following

(See Figures 16-18):

Install the vent connector avoiding unnecessary bends,

which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at

least 1/4-inch per foot (21 mm per metre).

Joints must be fastened by sheet metal screws or other

approved means. It must be supported to maintain

clearances and prevent separation of joints and dam-

age.

The length of the vent connector cannot exceed 75% of

the vertical vent height.

The vent connector must be accessible for cleaning,

inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor,

firewall, or fire partition.

It is recommended (but not mandatory) that a minimum

12 inches (30.5 cm) of vertical vent pipe be installed on

the draft hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for

obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney,

make sure the chimney passageway is clear and free of

obstructions. The chimney must be cleaned if previously

used for venting solid fuel appliances or fireplaces. Also

consult the “Natural Gas and Propane Installation Code,”

CAN/CSA B149.1-current edition as well as local and

provincial codes for proper chimney sizing and application.

The connector must be installed above the extreme

bottom of the chimney to prevent potentially blocking

the flue gases.

The connector must be firmly attached and sealed to

prevent it from falling out.

To aid in removing the connector, a thimble or slip joint

may be used.

The connector must not extend beyond the inner edge

of the chimney as it may restrict the space between it

and the opposite wall of the chimney (Figure 8).

LISTED LINED
CHIMNEY

DO NOT EXTEND
VENT BEYOND EDGE
OF CHIMNEY

VENT
CONNECTOR

MAINTAIN
CLEARANCE

SEAL

SLOPE

UP 1/4 IN.

PER FT.

(21 mm

PER

METRE)

MINIMUM

CHIMNEY TERMINATION VENT SYSTEM

SUPPORT
STRAP

1

1

MAINTAIN CLEARANCE

MAINTAIN
CLEARANCE

1

SEE END NOTES
ON NEXT PAGE

FIGURE 8.

CSA B149.1-current edition (Natural Gas and Propane

Installation Code) and all local/provincial codes.
The vent pipe installation must not be obstructed so as

to prevent the removal of exhaust gases to the outside

atmosphere.
IMPORTANT:

The use of vent dampers is not recommended by the

manufacturer of this water heater. Although some

vent dampers are certified by CSA International, this

certification applies to the vent damper device only

and does not mean they are certified for use on this

water heater.

Certified (listed) fuel gas and carbon monoxide (CO)

detectors are recommended in all applications and

should be installed using the manufacturer’s instructions

and local codes, rules, or regulations.

The venting system must be installed by a qualified

technician.

Draft Hood Installation

Align the legs of the draft hood with the slots provided.

Insert the legs and secure the draft hood to the water

heater’s top with the four screws provided as shown in

Figure 7.

SHEET METAL SCREWS (FOUR PROVIDED)

DRAFT HOOD

LEGS

LEGS

SLOT

SLOT

JACKET TOP

INSTALL THE DRAFT HOOD WITH
THE FOUR SCREWS PROVIDED.

FIGURE 7.

Do not alter the draft hood in any way. If you are replacing

an existing water heater, be sure to use the draft hood

supplied with this water heater.

Vent Pipe Size

It is important that you follow the guidelines in these

instructions for sizing a vent pipe system. If a transition to

a larger vent size is required, the vent transition connection

must be made at the draft hood outlet.

Vent Connectors

1. Type B, double wall, certified (listed) Vent Pipe.
2. Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance

from combustible surfaces when using type B double wall

vent pipe.
Vent connectors made of type B, double wall vent pipe

material may pass through walls or partitions constructed

of combustible material if the minimum listed clearance is

maintained.
Maintain a six inch (15.2 cm) minimum clearance from all

combustible surfaces when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for

water heaters located in attics and may not pass through

attic spaces, crawl spaces or any confined or inaccessible

Advertising