John Wood Atmospheric Gas (Standard) User Manual

Page 17

Advertising
background image

17

of the temperature and pressure relief valve (T & P)

or higher than normal water temperatures are the first

signs of thermosiphoning.

The domestic hot water line from the water heater

should be vertical past any mixing valve or supply line to

the air handler to remove air bubbles from the system.

Otherwise, these bubbles will be trapped in the air

handler heat exchanger coil, reducing the efficiency.

Do not connect the water heater to any system or

components previously used with non-potable water

heating appliances when used to supply potable water.

Some jurisdictions may require a backflow preventer in the

incoming cold water line. This may cause the temperature

and pressure relief valve on the water heater to discharge

or weep due to expansion of the heated water. A

diaphragm-type expansion tank suitable for potable water

will normally eliminate this weeping condition. Please

read and follow the manufacturer’s instructions for the

installation of such tanks.
Also see Water System Piping for additional instructions

on the safe and correct installation and operation of this

water heater.

TYPICAL MIXING VALVE INSTALLATION COMBINATION
SPACE HEATING/POTABLE WATER HEATING SYSTEM

MIXING
VALVE

HOT

WATER

OUT

UNIONS

IN

MUST BE VERTICAL TO
REMOVE AIR BUBBLES

DOMSETIC

HOT WATER

OUT

FLOW CONTROL

VALVE

PUMP

OUT

COIL

AIR

HANDLER

TO

AIR

HANDLER

SHUT-OFF

VALVE

EXPANSION TANK

VACUUM
RELIEF
VALVE

COLD WATER INLET

FIGURE 14.

Solar Installation

If this water heater is used as a solar storage heater
or as a backup for the solar system, the water supply
temperatures to the water heater tank may be in excess
of 120°F (48.9°C). A mixing valve or other temperature
limiting valve must be installed in the water supply line to
limit the supply temperature to 120°F (48.9°C).
NOTE: Solar water heating systems can often supply
water with temperatures exceeding 180°F (82.2°C) and
may result in water heater malfunction.

to the insulation to ensure that it is fully seated on the

T&P Relief Valve. Once seated, secure the insulation

with duct tape, electrical tape, or equivalent.

IMPORTANT: The insulation or tape should not block

or cover the T&P relief valve drain opening. Also, the

insulation or tape should not block or hinder access

to the manual relief lever (Figure 13B). Ensure

that a discharge pipe is installed into the T&P valve

discharge opening per the instructions in this manual.

4. Locate the hot water (outlet) & cold water (inlet) pipes

to the water heater.

5. Locate the slit running the length of a section of pipe

insulation.

6. Spread the slit open and slip the insulation over the cold

water (inlet) pipe. Apply gentle pressure along the length

of the insulation to ensure that it is fully seated around

the pipe. Also, ensure that the base of the insulation is

flush with the water heater. Once seated, secure the

insulation with duct tape, electrical tape, or equivalent.

7. Repeat steps 5 and 6 for the hot water (outlet) pipe.

8. Add additional sections of pipe insulation as needed.

T&P RELIEF VALVE

DRAIN LINE

T&P RELIEF

VALVE

MANUAL RELIEF

LEVER

T&P RELIEF VALVE INSULATION

FIGURE 13B.

Combination Space Heating/Potable

Water System

Some water heater models are equipped with inlet/outlet

connections for use with space heating applications. If this

water heater is to be used to supply both space heating

and domestic potable (drinking) water, the instructions

listed below must be followed.

Be sure to follow the manual(s) shipped with the air

handler system.

This water heater is not to be used as a replacement

for an existing boiler installation.

Do not use with piping that has been treated with

chromates, boiler seal or other chemicals and do not

add any chemicals to the water heater piping.

If the space heating system requires water

temperatures in excess of 120°F (48.9°C), a mixing

valve or an anti-scald device should be installed per its

manufacturer’s instructions in the domestic (potable)

hot water supply to limit the risk of scald injury.

Pumps, valves, piping and fittings must be compatible

with potable water.

A properly installed flow control valve is required to

prevent thermosiphoning. Thermosiphoning is the

result of a continuous flow of water through the air

handler circuit during the off cycle. Weeping (blow off)

Advertising