John Wood Takagi - 320H-520H User Manual

Page 16

Advertising
background image

16

Condensate Drain Connections

WARNING

Discharge condensate (acidic water) in
accordance with all local codes and com-
mon safety practices.

The 520H models are high efficiency condensing water
heaters that produce condensate (acidic water). The acidic
condensate generated in the secondary heat exchanger can
be neutralized by the Neutralizer accessory.

Case A: If a neutralizer is not required

Connect a 1/2" FPT X 3/8" (or 1/2") HB Adaptor to the
condensate drain port at the bottom of the water heater.
Connect a condensate drain tube to the 1/2" FPT X 3/8"
(or 1/2") HB Adaptor. The manufacturer recommends
the material of the condensate tube be either EPDM or
PVC.
Leave an adequate amount of space between the end
of the drain tube and the actual drain, to facilitate proper
drainage.

1/2"FPT X 3/8"

(or 1/2") HB

Condensate

drain port

Adequate

space

Drain

3/8" or 1/2"

Condensate

drain tube

1.

2.

3.

Case B: If a neutralizer is required (installing

the Neutralizer assembly)

Connect the 1/2" FPT X 3/8" MPT Adaptor to the conden-
sate drain port at the bottom of the water heater.
Connect the Neutralizer to the 3/8" MPT connection of
the adaptors. There is a flow direction indicator on the
neutralizer. Please orient the neutralizer in the proper
direction.
Connect a 1/2" drain tube to the other end of neutral-
izer.
Leave an adequate amount of space between the end
of the drain tube and the actual drain, to facilitate proper
drainage.

1/2"FPT X 3/8"MPT (Included

with Neutralizer accessory)

Condensate

drain port

Adequate

space

Drain

1/2" Condensate

drain tube

3/8"MPT X 1/2"HB (Included

with Neutralizer accessory)

Neutralizer cartridge (Included

with Neutralizer accessory)

1.

2.

3.

4.

Advertising