– 23 –

CALL FOR

HEAT ACTIVE

(Temperature low)

POWER INTERRUPTION System

shuts off

OR

PILOT FLAME FAILURE Valves close,

after recycle delay system recycles. If

recycles exceed maximum, timed

lockout is entered.

1

PILOT BURNER OPERATION

Pilot burner does not light. After retry delay system

retries. If retries exceed maximum, timed lockout is entered.

OR

Pilot burner lights. Ignition module senses flame current

and continues.

4

Damper energized.

2

STAGE 1

PREPURGE

STAGE 2

TRIAL FOR IGNITION

STAGE 3

MAIN BURNER OPERATION

STAGE 4

POSTPURGE

END

START

SPARK GENERATOR

POWERED

Pilot valve opens.

3

FLAME CURRENT

SENSED

Spark generator off,

Main Valve opens.

5

MAIN BURNER

OPERATION

Ignition module monitors pilot

flame current.

6

CALL FOR HEAT

INACTIVE

(Temperature at setpoint) Valves

close

7

Damper de-energized.

8

Figure 22 Sequence of Operation