If the PCS4 has never been configured and is still set for factory defaults, skip to step 4.
If not, perform a mode 4 system reset to restore the factory-set values (see “

Resetting

the Unit

” in the “Front Panel Features and Operations” section for the resetting

procedure).

NOTE: The PCS4 must be configured with the factory default IP address

(192.168.254.254) before you execute the ARP command, as described
below.

4.

On the computer, access the command prompt, then enter

arp

-s

, the desired new IP

address for the PCS4, a space, and finally the PCS4 MAC address (taken from the label
on the rear panel). For example:

arp

-s

10.13.170.15 00-05-A6-00-0A-90

A space must separate

arp

from the hyphen (

-

).

Figure 9.

ARP-S Command Screen

NOTE: After the

arp

-s

command is issued, the PCS4 changes to the new address

and starts responding to ping requests, as described in the next step.

5.

To verify that the new address has been set, execute a ping command by entering

ping

,

followed by the new IP address, at the command prompt.

NOTE: Ping is a utility or diagnostic tool that tests network connections. It is used to

determine if the host has an operating connection and is able to exchange
information with another host.

Example:

ping

10.13.170.15

Ping is a utility or diagnostic tool that tests network connections. It is used to determine
if the host has an operating connection and is able to exchange information with
another host.