Gb 1. use, Medium types, Installation – IMP Pumps NMT(D) SMART (C) User Manual

Page 15

Advertising
background image

-15-

GB

1. Use

The NMT SMART pumps are intended for forced circulation of the medium in

central heating systems. The pump constantly measures pressure and flow,

and adapts the speed to the selected pressure.

2.

Medium types

A medium that is pure water or a mixture of pure water and antifreeze, which

is appropriate for a central heating system, must be provided. The water

must meet water quality standards, such as: VDI 2035. The medium must

be free from aggressive or explosive additives, free from mixtures of mineral

oils and solid or fibrous particles. The pump should not be used for pumping

flammable, explosive media, and in an explosive atmosphere.

Permitted ambient and media temperature:

Ambient

temperature [°C]

Media temperature

min. [°C]

max. [°C]

0 to 25

2

110

30

2

100

35

2

90

40

2

80

Operation outside recommended conditions may shorten pump lifetime and

void the warranty.

3.

Installation

The pump must be mounted so that the electric motor axis is in a horizontal position

(see Figure 3.1). The permitted and prohibited positions are shown in Figure 3.2.

The arrow on the hydraulic part indicates the direction of the medium flow.

If there is not enough space for an electrical connection, the electric motor

part can be rotated so that the electrical connector is in a horizontal position.

A position with the electrical connector vertically above the motor is not

permitted (see Figure 3.3c). Before we must close the block valve on the

pressure and suction side of the pump and unscrew the screws (Figure 3.3).

We can turn the electric motor part as shown in Figures 3.3a or 3.3b.

Advertising