Constant speed

The pump operates with the currently set speed

13

A

Automatic mode (factory setting)

In automatic mode the pump automatically sets the operating pressure, depending on the hydraulic

system. By doing so, the pump finds the optimal operating position.

This mode is recommended in most systems.

The parameters cannot be set; they can only be scrolled through.

Proportional pressure (figure 5.3a)

The pump maintains the pressure with relation to the current flow. The

pressure is equal to the set pressure (H

set

on the drawing) at maximum

power; at 0 flow it is equal to 50% of the set pressure. In between, the

pressure changes linearly, relative to the flow.

In regulated mode we can only set the pump pressure (H

set

on the

drawing). We can only scroll through the other parameters.

Constant pressure (figure 5.3b)

The pump maintains the currently set pressure (H

set

on the drawing),

from 0 flow to maximum power, where the pressure begins to drop.

At constant pressure, we can only set the pressure (H

set

on the drawing)

which the pump will maintain. We can only scroll through the other

parameters.

Constant revolutions (figure 5.3c)

The pump operates with the currently set revolutions (RPM

set

on the

drawing).

In the unregulated mode, we can only set the revolutions at which the

pump will operate. We can only scroll through the other parameters.

Night mode

When the pump operates in night mode, it automatically switches between the selected operating curve

in the mode and night curve. The transition to the night mode depends on the media temperature in the

system.

When the night mode is prepared for operating, its icon illuminates and the pump operates in the

selected operating curve of the mode. When the pump identifies the media temperature fall by 15-20C°

(approximately during 2 hours), the icon starts to blink and the pump switches to the night curve. When

the media temperature rises again, the icon stops blinking and the pump passes over to the operating

curve in the selected operating mode.

The night mode operates only in combination with the above indicated modes. It is not an independent

operating mode.

5.6.

Setting the pump to the factory settings

To restore factory settings to the pump, it is necessary to press and hold all three keys for 5 seconds. The pump

is set to the automatic mode of operation. The previously set values for pressure and revolutions will be deleted.

-

Max.

H

Q

Hset

2

Proportional pressure

+

H

set

+

H

Q

H

set

Constant pressure

-

Max.

Min.

H

Q

Constant revolutions

RPM

set

Max.

+

-

(RPMset on the drawing).

In the unregulated mode, we can only set the speed

at which the pump will operate. We can only scroll

through the other parameters.

Night mode

When the pump operates in night mode, it automatically switches between

the selected operating curve in the mode and night curve. The transition to

the night mode depends on the media temperature in the system.

When the night mode is prepared for operating, its icon illuminates and the

pump operates in the selected operating curve of the mode. When the pump

identifies the media temperature fall by 15-20C° (approximately during 2

hours), the icon starts to blink and the pump switches to the night curve.

When the media temperature rises again, the icon stops blinking and the

pump passes over to the operating curve in the selected operating mode.

The night mode operates only in combination with the above indicated

modes. It is not an independent operating mode.

5.6.

Setting the pump to the factory settings

To restore factory settings to the pump, it is necessary to press and hold all

three keys for 5 seconds. The pump is set to the automatic mode of operation.

The previously set values for pressure and revolutions will be deleted.

5.7. Twin-head pumps NMTD SMART (C)

Pumps have a common hydraulic housing that is equipped with a change-

over flap and two pump heads, separately connected to the electrical grid.

Pumps that communicate with each other. – NMTD SMART C

Pumps without an communication option – NMTD SMART

With this use, we recommend that night mode isn't used.