5 specifi cations, 0 system overview, continued, Noise – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 18: Acoustic noise, System size: ce-3x pn-6x, Fuel consumption, Common to all models, Optional features

Advertising
background image

18

042-288-B0-001, Rev. A

1.0

System Overview, continued

1.5 Specifi cations

Model

CE-3x2 5.0kW

PN-6x-T 7.5kW

DC Output Voltage:

-51.5 to -52V @ no load

-51.5 to -52V @ no load

DC Output Load Regulation:

0.5V

0.5V

Output Current:

52V @96A max.

52V @ 144A max.

Noise

Voiceband:

<54dBrnc

<54dBrnc

Wideband:

<100mVrms in any 3kHz bandwidth from 10k to 20mHz

<100mVrms in any 3kHz bandwidth from 10k to 20mHz

Broadband:

<250mVp-p from 20 to 100mHz

<250mVp-p from 20 to 100mHz

Engine:

398cc, air-cooled, single OHV
10.5hp (using natural gas fuel)

624cc, air-cooled, twin OHV
13.1hp (using natural gas fuel)

RPM (Variable Speed):

2800 to 3600RPM

2100 to 3450RPM

Acoustic Noise

dBA 10' @ 100% rated load:

68.5 avg.

70.3 avg.

dBA 20' @ 100% rated load:

62.5 avg.

64.3 avg.

dBA 10' @ 70% rated load:

66.9 avg.

66.4 avg.

dBA 20' @ 70% rated load:

60.9 avg.

60.4 avg.

System Size:

CE-3x

PN-6x

Height (in/cm):

44/111.8

36/99.1

Width (in/cm):

26/66

39.25/99.7

Depth (in/cm):

24/61

24/61

Weight (lb/kg):

395/179.2

338/153.3

Fuel Consumption

Natural Gas: 1000BTU/ft

3

80ft

3

/hr

156ft

3

/hr

Propane Gas: 2520 BTU/ft

3

1.1gal/hr

1.48gal/hr

40ft

3

/hr

54ft

3

/hr

4.62lb/hr

6.24lb/hr

Gas Inlet Pressure:

0.5 to 2 PSI Inlet pressure
(Please contact Alpha Technologies for low pressure)

0.5 to 2 PSI Inlet pressure
(Please contact Alpha Technologies for low pressure)

Ignition Charger Voltage:

13.5Vdc

13.5Vdc

Ignition Charger Current:

6A max.

6A max

Remote Interface Length:

50ft. max
Distance depends upon proper installation, de-rating,
and wire gauge. Please contact Alpha Technologies for
remote interface length usage.

25ft. max
Distance depends upon proper installation, de-rating, and
wire gauge. Please contact Alpha Technologies for remote
interface length usage.

Agency Compliance:

UL2200, NFPA 37/54/58 and 70, CSA 22.2, FCC Class A

UL2200, NFPA 37/54/58 and 70, CSA 22.2, FCC Class A

Common to All Models

Fuel System, Controls & Monitoring:

The controls and fuel system meet applicable sections of NFPA 37, 54, and 58 for automatic unattended operation of
remotely located generators. Full system control and status monitoring included

Sensors:

Gas hazard, pad shear, water intrusion & tamper

Safety shutdowns:

Low oil pressure
Water intrusion
Pad shear
Gas hazard (propane or Natural Gas)

Over speed
Over crank
Over temp
Low fuel pressure shutdown (Propane only)

Optional Features

Optional Integrated Propane
Storage: (5kW APU only)

For locations where gas is not available, Alpha offers the CE-G propane enclosure for use with the 5kW APU system.
Contact local propane supplier for proper tank sizing. Fully CSA & NFPA compliant, and designed for curbside
applications.