Alpha Technologies Spill Control Barrier System User Manual

Page 7

Advertising
background image

Alpha Industrial Power

Spill Control Barrier System

Installation Manual

Page 6 of 25

3.6

The following tools and supplies are recommended for a quick and
thorough Barrier installation:

7/16 inch box end or combination wrench
putty knife
tape measure
several sheets of sandpaper, 100 grit
roll of 1 inch masking tape
goggles, chemical resistant gloves and respirator (as needed) for
installers’ paper towels or shop rags
rubbing alcohol

3.6.1

Additional supplies needed for Spill Barrier with floor coating version
only:
small metal ruler with 1/64” increments or wet film thickness gauge.

The Coating Installation standard Tool Kit (part number
5BNK0001) contains: small rotary stirring tool, two v-notch trowels,
four v-notch spreaders, one masking tape, two brushes, two gloves,
two rags, two putty knives, one 3-piece extension, one 1-1/2 inch
spiked pin roller, one pair goggles, and two sheets sandpaper.
(Other kits available upon request)

4. Floor Preparation

4.1

The installer or site/equipment engineer must ensure that sufficient aisle space
will remain once the Barriers have been installed. There should be a minimum
of 30 inches between Barriers. Aisle spacing at the end of each rack may be as
little as 24 inches, providing no conflict exists with battery maintenance
requirements. The aisle spacing, including the space between the surrounding
Barriers, should be sufficient to permit all required maintenance (including battery
installation and removal). See the National Electric Code or contact the local authority
having jurisdiction for further clarification regarding aisle clearances.

4.2

After clearances have been verified, locate and mark the outline of the
Barrier using the Barrier’s dimensions and a tape measure. The Barrier should
be centered around the rack with at least 1 inch clearance in all directions
to meet 1995 Uniform Fire Code article 64 requirements.

Advertising