www.climacoolcorp.com

Note: Contact factory for network points list

Connection Type

The default CONNECTION TYPE for the BACnet over

ETHERNET to the WEB PORTAL is a CAT5 Cable via an

RJ-45 connector. The connector plugs into the Ethernet

10BaseT port.
Note: If these settings need to be changed, please contact a

ClimaCool Representative.

Ethernet Network

The Master Controller is equipped with an interface which

may be connected directly to the Ethernet network using

the 10BaseT port. To prevent circular routes, the Master

Panel will be configured only for BACnet/IP. The BACnet/IP

Network Number will be defaulted to 516800. The BACnet/

Ethernet router configuration will be disabled and the

Ethernet Network number set to 0.
Note: If these settings need to be changed, please contact a

ClimaCool Representative.

IP Address

The following is the default settings for the IP Address for a

typical Master Controller:

IP .............................................192.168.17.100

Subnet Mask...........................255.255.255.0

Gateway ..................................192.168.17.1

Note: If these settings need to be changed, please contact a

ClimaCool Representative.

Device Instance of Master Controller

The device instance number for the Master Controller is

516800. The “address” number of the Master is “01,” as

identified by the two rotary switches on the Master PCB

(one rotary switch is for 10’s digit and the other is for the 1’s

digit), (See Figure 1 – page 4).
Note:
If these settings need to be changed, please contact a

ClimaCool Representative.

Device Instance of Module Controller

The device instance number for the FIRST Module

Controller is 243002. The “address” number of the FIRST

module controller is “02.” Similarly, the device instance

number of the SECOND Module Controller is 243003.

The “address” number of the SECOND Module Controller

is “03.”