The CoolLogic Control System provides leaving chilled and

hot water liquid temperature control algorithms which

maintain precise temperature control for cooling, heating,

heat recovery and simultaneous heating and cooling

applications. A compressor run time equalization sequence

is given to ensure even distribution of compressor run

time throughout the entire chiller bank. Chiller power

consumption is minimized by indexing the most effi cient

stages of cooling, optimizing heat transfer surface.
The ClimaCool

®

Ultimate Chiller Solution, “UC” and “UG”

series, modular water-cooled chillers utilize the CoolLogic

Control System to incorporate one or more modules. The

controls are divided into two separate sections - the Master

Control Panel and the module controller. The Master Control

Panel governs all signifi cant events, timing and compressor

staging, providing operator interface for all levels of setting

and retrieving data

.

A single Master Control Panel has the

ability to control a bank of modules with each unit having

a unique address code by setting the two rotary switches

of the master and each module controller. The Master

Controller is address #01, module #1 is address #02, and so

on (see fi gure 1 on page 4).
The module controller resides at each module location

which senses and analyzes all pertinent data specifi c to

that module’s compressor and water fl ow operations.

CoolLogic Control System Wiring

A separate 115 volt power supply is required to power the

CoolLogic Master Control Panel. Communication between

the Master Control Panel and chiller modules requires a

simple two-conductor 16 gauge shielded cable rated at 60°C

minimum, daisy chain connection. Control wiring cannot be

installed in the same conduit as line voltage wiring or with

wires that switch highly inductive loads such as contactor

and relay coils. Refer to the Power Distribution schematic on

page 47 of this manual for more information. All wiring shall
be in compliance with all local and national codes.

Safety

Throughout this manual warning, danger, caution and

attention notices appear. Read these items carefully before

attempting any installation, service or troubleshooting of

the equipment. All labels on unit access panels must be

observed.

DANGER: Immediate hazardous situation which, if not

avoided, will result in death or serious injury.
WARNING: Potentially hazardous situation which, if not

avoided, could result in death or serious injury.
CAUTION: Potentially hazardous situation or an unsafe

practice which, if not avoided, could result in minor or

moderate injury or product or property damage.

CoolLogic Control System

DANGER

!

• Electric shock hazard!

• May result in injury or death!

• Disconnect power supply(ies)

before servicing!

• Refer servicing to qualified

service personnel.

• Risque de choc électrique!

• Résultat de mai dans dommages

ou la mort!

• Debrancher avant d’entreprendre

le dépannage de l’appareil!

• Consulter un réparateur qualifie

pour le dépannage.

DANGER

!

CAUTION

ATTENTION

!

!

• Unit to be serviced by qualified

personnel only.

• Refrigerant system under

pressure.

• Relieve pressure before using

tourch.

• Recover refrigerant and store or

dispose of properly.

• Confier la maintenance á un

technicien qualifie.

• Le systéme frigorifique sous

pression.

• Décomprimer avant d’exposer á

la flamme.

• Récuperér le frigorigene et le

stocker ou le détrire

correctement.

RECOVER

REFRIGERANT

WARNING!

WARNING! To avoid possible injury or death due to electrical

shock, open the power supply disconnect switch and secure it

in an open position during installation.

CAUTION!

CAUTION! Use only copper conductors for field installed

electrical wiring. Unit terminals are not designed to accept

other types of conductors.