Starting the chiller, Coollogic control system operator interface – ClimaCool CoolLogic Control System User Manual

Page 5

Advertising
background image

5

www.climacoolcorp.com

Figure 4

Starting the Chiller

When power is fi rst applied to the Master Control Panel,

a 45 second initialization period will occur. The display will

show the home screen (Figure 5). Once power has been

applied to the Master Control Panel various display screens

are accessible by several methods. From the “Home”

screen, you are easily guided to the main menu listings for

the following categories by pressing one of the bottom four

menu buttons:
Figure 5: Home Screen

At the end of this delay, the fi rst compressor will start and

after a fi ve minute timeout, the display will change to the

default screen (Figure 6).
Figure 6: Default Screen

Confi guring the Master Controller (I/O Pro 812u)

for ARC156

1. Turn off the Master Controller’s (I/O Pro 812u) power
2. Using the rotary switches, set the Master Controller’s

address. Set the Tens (10’s) switch to the tens digit of the

address, and the Ones (1’s) switch to the ones digit.

Example (Figure 1): If the Master Controller’s address is 01,

point the arrow on the Tens (10’s) switch to 0 and the arrow

on the Ones (1’s) switch to 1.
Figure 1

Figure 2

3. Communication selector (Figure 2 above) (DIP Switches

1-8 are all OFF).

4. Port 1 is the only port that speaks BACnet over ARC156.

Connect the communications wiring to Port 1 in the

screw terminals labeled Net+, Net-, and Shield (Gnd).

The module controller references GND, and the master

controller references SHIELD.

5. Set Port 1 Mode jumper to ARC156 (Figure 3).
Figure 3

6. Turn on the Master Controller’s power.
7. Set the correct network number to the unique ARC156

network at the jobsite.

CoolLogic Control System Operator Interface

The CoolLogic Control System off ers an easy-to-use operator

interface keypad (Figure 4) which includes a four-line by

40 character, back-lit LCD display panel, which is easy to

navigate using logically grouped menus. This enables the

user to access important information concerning set points,

active temperatures, pressures, operating modes, alarm

conditions, chiller scheduling, servicing, diagnostics

and more.

chill water in: 0000.0f / cool spt: 0000.0f
chill water out: 0000.0f / tot stg want: 00
cond water in: 0000.0f / tot stg on: 000
cond water out: 0000.0f / mode : cooling
chil water flow : yes / heat spt: 0000.0f
cond water flow : yes / status: unloading
[--> status] [--> setup] [--> service] [--> alarm]

climacool corp. coollogic

date: mm/dd/yyyy time: hh:mm am

chws temp: 0000.0f cwr temp: 0000.0f

press any key to continue

BACnet-over-

ARC156

Baud - N/A

– Port 1
– IP Address
– Enhanced Access

Port