n Performances in hot mode with outside air temperature

at +2°C and outlet water temperature at +35°C (in
accordance with EN 14511–2)

AWHP

4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR

Calorific output - A2/W35

kW

3.76 3.87

5.93

10.19

10.19

11.38

11.38

11.62 14.70

COP hot - A2/W35

3.32 3.26

3.20

3.20

3.20

3.27

3.27

3.01

3.10

Absorbed electrical power - A2/W35 kWe 1.13 1.19

1.85

3.19

3.19

3.48

3.48

3.86

4.74

Nominal amperage - A2/W35

A

6.1

6.1

8.2

10.7

6.2

14.6

8.4

9.7

11.8

n Performances in cold mode with outside air

temperature at +35°C and outlet water temperature at
+18°C (in accordance with EN 14511–2)

AWHP

4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR

Cooling output

kW

3.84 4.69

7.90

11.16

11.16

14.46

14.46

17.65 22.2

EER

3.80 3.80

3.99

4.68

4.68

4.43

4.43

3.8

3.8

Absorbed electrical power kWe 0.72 1.15

2.0

2.35

2.35

3.65

3.65

4.65

5.84

n General values

AWHP

4 MR

6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR

27 TR

Sound pressure

(1)

dB(A) 41.7

41.7

43.2

43.4

43.4

47.4

47.4

51.8

53

Nominal water flow

(ΔT = 5K)

m

3

/h 1.04

1.04

1.47

1.88

1.88

2.67

2.67

3.8

4.6

Manometric height

available at nominal

flow rate

mbar 618

618

493

393

393

213

213

-

-

Nominal air flow rate m

3

/h 2100

2100

3000

6000

6000

6000

6000

8400

8400

Power voltage of the

outdoor unit

V

230 V~ 230 V~ 230 V~ 230 V~

400 V3~ 230 V~

400 V3~ 400 V3~

400 V3~

Sound output

(2)

dB(A) 63.7

63.7

65.2

65.4

65.4

69.4

69.4

73.8

75

R410A refrigerant

kg

2.1

2.1

3.2

4.6

4.6

4.6

4.6

7.1

7.7

refrigerant piping

connection (Liquid-

Gas)

inch

1/4-1/2 1/4-1/2 3/8-5/8 3/8-5/8

3/8-5/8

3/8-5/8

3/8-5/8

3/8-3/4 or

3/8-1

1/2-3/4 or

1/2-1

Max pre-loaded

length

m

10

10

10

10

10

10

10

30

30

Weight (empty) -

Outside unit

kg

42

42

75

118

118

130

130

135

141

(1) 5 m from the appliance, free field.

(2) Test conducted in accordance with the standard NF EN 12102

AWHP-2 MIT-IN-2 iSystem

6. Technical specifications

31/03/2014 - 7616372-001-02

30