Faults

Fault

Possible cause

Correction

Valve does not
switch

Operational voltage too low or
not present;

Check the electrical supply connections.

Ensure that the electrical power supply is the same as

that spe-cified on the rating plate.

Manual override not in neutral
position;

Set the manual override to the zero position.

Compressed air supply not
available or insufficient.

Carry out the dimensioning of the compressed air
connection with volumes as large as possi-ble (including
that of upstream pressure regulators, service units, cut-
off valves etc.)

Minimum operational pressure

2 bar

Valves switch
with a delay, or
exhaust
through the
venting ports:

Compressed air supply not
available or insufficient;

Führen Sie die Druckversorgung möglichst großvolumig

aus (auch bei vorgeschalteten Geräten wie

Druckreglern, Wartungseinheiten, Absperrventilen usw.).

Mindestbetriebsdruck

2 bar

Valves are not in the starting

position (whitout current)
during pressure build-up.)

Appley pressure to the valve block before you switch the
valves

Insufficient venting of the

exhaust channels due to
silencers that are too small or
are soiled (back-pressure);

Use silencers or expansion channels with sufficient

dimensions.

Clean soiled silencers.

Impurities or foreign matter in

the pilot valve or main valve.

Blast through the exhaust cahnnels with pulsed

compressed air, to blow out impurities. Install a new pilot
or main valve if these measures bring no improvement.

Leaking valve
block:

O-rings between the modu-
les missing or damaged;

Check for leaks and for missing seals.

Missing or incorrectly posi-

tioned profile gaskets be-
tween the valve and the

baseplate.

Install the missing seals and replace damaged seals.