Operating mode manual, Displays of the manual mode, Meaning of the keys in the manual mode – Burkert Type 8630 User Manual

Page 90

Advertising
background image

88 - 8630

O

PERATION

AND

CONTROLLER

FUNCTIONS

Displays of the MANUAL mode:

The last display set in the AUTOMATIC mode is shown.
By selecting

POS_XXX, the actual position of the valve actuator can be checked.

MANUAL
mode

Valve closes
at normal
speed

AUTOMATIC
mode

No
operating
action

release

(> 5 sec.)

Configuration

Menu item

Release key

Release key

Valve closes
fast

Valve opens
at normal
speed

Valve opens
fast

release

END

Operating mode MANUAL

(yellow LED off)
In the manual mode, the valve can be opened and closed by hand.

Meaning of the keys in the MANUAL mode:

Press the

key in the MANUAL mode:

Pressurization of the actuator
SFA: valve opens
SFB: valve closes
SFI:

port 2.1 pressurized

Press the

key in the MANUAL mode:

Venting of the actuator
SFA: valve closes
SFB: valve opens
SFI:

port 2.2 pressurized

Hold down the

key and simultaneously press the

:

Fast pressurization

Hold down the

key and simultaneously press the

:

Fast venting

NOTE

SFA: actuator closing by spring force
SFA: actuator opening by spring force
SFI:

actuator with double action

+

+

Advertising