4 electrical installation as-interface – Burkert Type 8695 User Manual

Page 17

Advertising
background image

17

Electricalinstallation/displayelements

ye

gn

Bo

t

To

p

To

p

Bo

t

ye

gn

Jumper for assignment of
end position LEDs

End position LED green

End position LED yellow

Valve LED yellow (pilot valve)

Status LED yellow

Fig. 11: Display elements 24 V DC

led

state

End position LED green

on

End position bottom

2)

End position LED yellow

on

End position top

2)

LED Valve yellow

on

Pilot valve is actuated

Status LED yellow

flashing

Teach function is running

flickers

Puck PCB not available

Tab. 3: Display elements 24 V DC

note!

damage or malfunction due to penetration of dirt and humidity.

▶ To observe protection class IP65 / IP67, screw the transparent

cap in all the way.

2)

Color setting ex works. Can be set via jumper (see “Fig. 11”).

9.4 electrical installation as-interface

9.4.1 connection with circular plug-in

connector m12 x 1, 4-pole, male

Pin 4:

NC

Pin 1:

Bus +

Pin 3:
Bus –

Pin 2:
NC

Fig. 12: Connection with circular plug-in connector, AS-Interface

pin

designation

configuration

1

Bus +

AS-Interface bus line +

2

NC

not used

3

Bus –

AS-Interface bus line -

4

NC

not used

Tab. 4: Pin assignment of circular plug-in connector for AS-Interface

Connect the control head according to the table.

The teach function can now be used to automatically determine
and read in the end positions of the valve (description of the teach
function see chapter “10 Teach function”).

For the bus variant AS-Interface, the teach function can also
be started via the bus protocol.