English – Burkert Type 8695 User Manual

Page 23

Advertising
background image

23

Electricalinstallation/displayelements

status of the bus status led

led

device status explanation

troubleshooting

Off

No power
supply /
not online

Device is not supplied
with voltage
Device has still not
ended Duplicate MAC
ID Test (test lasts
approx. 2 sec)
Device cannot end
Duplicate MAC ID Test.

Connect other devices,
if the device is the only
network subscriber,
Replace device
Check baud rate
Check bus connection

Green

Online, con-
nection to
master exists

Normal operating status
with established con-
nection to the master

Flashes
green

Online, without
connection to
master

Normal operating status
without established
connection to the
master

Flashes
red

Connection
time-Out

One or more I/O con-
nections are in Time-
Out state

New connection estab-
lishment by master to
ensure that the I/O
data is transmitted
cyclically.

Red

Critical fault

Another device with the
same MAC ID address
is in the circuit
No bus connection
due to communication
problems

Check baud rate
If required, replace
device

Tab. 12: Status of the bus status LED

status of the device status led

led

device status

explanation

Off

No supply

Device is not supplied with voltage

Green

Device is working

Normal operating status

Tab. 13: Status of the device status LED