Technical data for the overall system – Burkert Type 8644 User Manual

Page 29

Advertising
background image

8644/Rockwell - 25

S

YSTEM

D

ESCRIPTION

Technical data for the overall system

Voltage supply:

Rated voltage

24 V/DC

Tolerance

- 15% / + 20%

Valve types 0460, 0461

- 10% / + 10%

Valve type 6524 (2x 3/2-way)

- 15% / + 10%

Current carrying capacity:

Logic area

1 A

24 V area

2.5 A

Maximum current consumption:

I_module

proportion of current in the logic area of the basic electronic modules
max. 75 mA

I_valve

valve current before and after power reduction

Temperature:

Storage temperature

- 20 to + 60 °C

NOTE

The admissible ambient temperature is depent on the modules used. During assembly, the
crucial factor is the most critical module.

Valve type 6524, 6525, 6526, 6527

0 to + 55 °C

Valve type 0460, 0461

0 to + 50 °C

After the field bus nodes 1734-APB, 1734-ADN and 1734-PDN, 13 modules can be placed
in each case. After this, 13 further modules may be connected in each case by attaching
power supply units. The total number of modules must not exceed 63.

Full configuration, 11 mm add-on dimension

max. 64 valves

Full configuration, 16.5 mm add-on dimension

max. 32 valves

NOTE

Valve type

Valve current

before power reduction

after power reduction

6524

43 mA

28 mA

6524

(2 x 3/2-way)

43 mA

18 mA

6525

43 mA

28 mA

6526

[1 W/ 2 W]

42/85 mA

33/52 mA

6527

[1 W / 2 W]

42/85 mA

33/52 mA

0460

41 mA

-

0461

41 mA

-

Advertising