36

GB

Safety venting and external / internal
auxiliary control air for fi eld bus, multipole
and RIO modules

46

Safety vent M5, D6, D4, D1/4“

47

Switching between external / internal auxiliary con-
trol air. Connector 12/14 must be closed for internal
auxiliary control air.

CAUTION!

Danger from excessive pressure in the housings!

In the event of error, the safety ventilation connector on the
housing of the fi eld bus / multipole module accumulates the
air and conducts it out of the modules.

The safety ventilation connector must always be connected
in order to maintain the protection class.
In order to guarantee the protective function, the safety
ventilation must not be closed.

37

GB

COMBINATION MODULE
KM P04 (PO2)

5)

/ DI4

6)

Technical Data

Supply voltage
(transmitter)

24 V; -15 % / +20 %

Supply current
(transmitter)

max. 700 mA (in the system)

Connections

4 x M8, 3-pin, jack

2 x M12,

4-pin, double allocation, plug

Displays

4 LEDs for the status of the

feedback

4 (2) LEDs for switching status

of the valves

Inputs
Logic level high

13 ... 30 V

Logic level low

0 ... 5 V

short-circuit-proof

yes

Input delay in connec-
tion with fi eld bus
module

typical 4 ms

5)

PO: Pneumatic Output

6)

DI: Digital Input

38

GB

KM PO4 / DI4

2 * 2 x 3/2-way valve with M8 connections

8

FE contact

21

DIN rail mounting

27

Labelling fi elds

29 ...
32

Emergency manual
control valve 1...4

33 ...
36

Connections DI
1...4 (M8)

37 ...
40

Labelling fi elds DI
1...4

49

LEDs for switch-
ing status V1...4
- valve functions
1...4

PIN connection

PIN

DI

1

... DI

4

1

+24 V

3

GND

4

IN

1

... IN

4

39

GB

KM PO4 / DI4

2 * 2 x 3/2-way valve with M12 connections

8

21

49

31

32

33

34

29

37

30

38

39

40

27

8

FE contact

21

DIN rail mounting

27

Labelling fi elds

29 ...
32

Emergency manual
control valve 1...4

33 ...
34

Connections DI
1/2, DI 3/4 (M12)

37 ...
40

Labelling fi elds DI
1...4

49

LEDs for switching
status V1...4 -
valve functions 1...4

PIN connection

PIN

PIN

1

+24 V 2

IN
(X+1)

3

GND

4

IN X

Advertising