Rio module technical data, Overview, Electrical connections – Burkert Type 8645 User Manual

Page 9: Pneumatic connections

Advertising
background image

32

GB

RIO MODULE

Technical Data

Operating voltage

24 V; -15 % / +20 %

Residual ripple

2 V

ss

Current consumption
Inputs / Logic

max. 1 A

Outputs

max. 4 A (M12)

Overview

Detail drawing

Diagnostic / Status LEDs (20)

RIO

Status

U

i

Logic vol-
tage

F

S

Error
select

U

O

Output
voltage

F

N

Error
number

U

S

Sensor
voltage

33

GB

13

22

50

20

8

9

23

51

52

53

18

19

26

8

FE contact

9

FE contact

13

Type plate

18

Rotary encoder switch
(x1)

19

Rotary encoder switch
(x10)

20

Diagnostic/Status LEDs
(see detail drawing)

22

Label panel Power

23

Connection Power

26

Diagnostic and update
interface

50

Label panel RIO IN

51

Connection
RIO IN (M8)

52

Label panel RIO OUT

53

Connection
RIO OUT (M8)

34

GB

Electrical connections

Voltage supply

M12, plug 4-pin, max. 4 A

RIO incoming

M8, jack

RIO outgoing

M8, jack

Address setting

via rotary encoder switch

Address range

0 ... 49

Integrated diagnostic
interface

3-pin, (RM 2.54)

Diagnostic LEDs

2 x RIO status

2 x fault indication

3 x supply voltage

Connection table

PIN

RIO IN /
RIO OUT

Power / Supply Voltage

1

CAN_H

+24 V Output (U

o

)

2

CAN_L

+24 V Logic / Sensors (U

i

)

3

FE

GND Logic / Sensors (U

i

)

4

_

GND Output (U

o

)

35

GB

PNEUMATIC CONNECTIONS

Field bus- / Multipole- /
RIO-module

Intermediate module
(Inside)

42

44

43

45

1

3/5

82/84

12/14

Ext.

Int.

Push

Turn

42

44

43

45

47

42 Auxiliary control air

M5, D6, D4, D1/4“

43 Pilot exhaust air

M5, D6, D4, D1/4“

44 Exhaust air

G1/4“, NPT1/4“, D10

45 Compressed air supply

G1/4“, NPT1/4“, D10

47

Switching between external / internal auxiliary con-
trol air. Connector 12/14 must be closed for internal
auxiliary control air.

Advertising