12

GB

INSTALLATION

CAUTION!

Danger due to electromagnetic fi elds!

If the FE connectors are not connected, the EMC-law condi-
tions are not adhered to!

Pay attention to the correct positioning of the gaskets
around the electronic and pneumatic components.

Start with the fi eld bus / multipole module.
The sequence of modules is random to the right of the
fi eld bus / multipole module.

A) Wall mounting

8

FE contact
(connect via FE rail)

8a FE rail

9

Screw (separate FE
connection)

10 Mounting straps

13

GB

Proceed with wall mounting as follows:

fi rst, fasten the fi eld bus / multipole module to the two
mounting points on the wall

remove the blue connection bracket

unbolt the 3 pinlocks (module) (see illustration: DIN-track
assembly
)

then push the next module onto the fi eld bus / multipole
module

fi x the module to the wall (as above)

connect the modules by pressing and turning the 3
Locking bolts (modules) to the right (90°). (Exception:
Terminal module)

install all the modules in the same way

Block open the blue connection brackets between all
the modules

install the FE connection on the front of the fi eld bus
module

connect the FE contacts (8) via the FE rail

connect the FE rail to FE

14

GB

B) Mounting on a DIN rail

11

DIN rail mounting

12

Locking pins (modules)

The FE contacts on the modules are connected via the
DIN rail that also has to be connected to FE.
The screw (9) on the fi eld bus module is connected
to FE separately.

15

GB

Proceed with rail mounting as follows:

install the modules from left to right

remove the blue connection bracket

unbolt the three pinlocks (module)

open the DIN rail mounting

place the module onto the DIN rail

push the module to the left up to the block (This point does
not apply for the fi eld bus / multipole module.)

connect the modules by pressing and rotating the 3
locking bolts (modules) to the right (90°) (Exception:
Terminal module)

screw on the DIN rail mounting tightly,

install all the modules in the same way,

block open the blue connection brackets between all
the modules.