GB

Pneumatic power data

Valve type

6524

3/2-way

6525

5/2-way

6524

2x 3/2-way

6526

3/2-way

652

7

5/2-way

Circuit functions

1)

C/D

H

2x C C/D

H

stacking size [mm]

11

16.5

Pneumatic connections:

Plug-and-socket
connections

D4

5)

, D6, D1/4“

5)

D8

Threaded connections

M5, M7

G 1/8“,

NPT 1/8“

Orifi ce [mm]

4

6

QNn

2)

[l/min]

300

700

Opening time

3)

10 % [ms]

35

80

Closing time

3)

10 % [ms]

45

90

Pressure range

4)

[bar]

2.5 ... 7

2 ... 8

with auxiliary control air

6)

1 ... 7

1 ... 8

Output [W]

0.3

1)

C=NC (normally closed), D=NO (normally open)

2)

Flow rate QNn value air [l/min]: Measured at +20 °C,

pressure 6 bar at the valve inlet and 1 bar pressure difference

3)

Switching times [ms]: measured in accordance with ISO 12238

17

GB

These values may differ, depending on the valve type and
function (see operating manual, chapter Confi guration and
Function of the Modules / Integratable Valves
)

4)

Pressure data [bar]: Overpressure with respect to atmospheric

pressure

5)

Connection variants on request

6)

Versions for vacuum on request

WARNING!

Hazard due to high pressure!
Interference with the system will result in an acute risk of
injury.

Change the fi tted valves only when AirLINE Ex is depres-
surised.

When using a P shut-pff at the corresponding valve posi-
tion, the valves can also be exchanged under pressure.

Diagnosis (Elektronic module)

Group fault display: Yes, locally at the electronic module
(red

LED)

Diagnostic function (can be read out via Profi bus):

Channel status diagnosis (channel open, channel short
circuit).

Individual switching cycle counter for each channel with
warning limits for pilot valve and connected actuator.

18

GB

Pneumatic supply module

Illustration:
Pneumatic supply
module

11

12

19
13

14

11 Clamping bolts (2x) for system connection

Pneumatic connections:
12 R/S-3/5

13 X

14 P/1

19 Inclined tie rod

19

GB

Technical data

Pneumatic
connections

G 3/8“, G 1/8“ or
NPT 3/8“, NPT 1/8“

Dimensions [mm]

Appr. 50 (per station 44) x 70 x 75

Material

PA

Weight [g]

150

Pneumatic Connections

Pos. Marking Function

Version
G

NPT

12

R/S-3/5

Exhaust air

3/8“

3/8“

13

X

Control
EXT: Auxiliary control air
INT: Pilot exhaust air

1/8“

1/8“

14

P/1

Compressed air supply

3/8“

3/8“

Supplementary information can be found in the opera-
ting manual also in chapter Confi guration and Function
of the Modules / Supply Slices.