24

GB

Terminal
module

Illustration:
Terminal module

33

32

20

18

18
34

15

32 Hinge contour for the electronic module
18 Power-Bus
20 Communication bus
33 Abutment for the electronic module
34 Plug for the electronic module

1)

15 Unlocking slide (only with ID no. 173 369)

1)

not with ID no. 173 368, 173 369

Technical data

ID no.

173 368 173 369 173 370

173 371

Application

Supply slice

Supply slice

left, middle

right

44 mm

66 mm

Dimensions
[mm]

55 (Stacking size 44 mm)

x 190 x 45

66 x 190 x 45

Weight [g]

150

210

Material

PBT, PC (Gehäuse)

P

V

(Power loss) [W]

0

2)

Type of protection

II 2 G Ex e [ia/ib] IIC T4

2)

The module contains no electrically active components.

25

GB

Elektronic module

Illustration:
Electronic module

21
22

10

27

35

21 Module status red LED

22 Channel status green LED

10 Hinged cover fl ap

35 Valve connector

27 Labelling panel, slot-in

The electronic module is electrically active (function:
Digital output module) and must be planned accor-
dingly in the programs for the hardware confi guration
(e. g. Siemens Step7™).

26

GB

Technical data

ID no.

171 941 171 942

171 943

171 944

Valve outlets

4

8

4

8

Dimension
[mm]

44 x 120 x 135

(for 11 mm valves)

66 x 120 x 135

(for 16.5 mm valves)

Weight [g]

230

250

270

290

Material

PBT, PC (Housing)

Power con-
sumption [mA]

250

310

250

310

Power loss [W] max. 2.9 max. 3.6

max. 2.9

max. 3.6

Status displays

LED (red) for the module status

LED (green) per channel (valve function)

Type of
protection

II 2 G Ex ib IIC T4

Diagnosis

Group fault display: Yes, locally at the electronic module
(red

LED)

Diagnostic functions (can be read out via Profi bus):

Channel status diagnosis (channel open, channel short
circuit.)

Individual switching cycle counter for each channel with
warning limits for pilot valve and connected actuator.

27

GB

Pneumatic valves type 6524/6525

Technical data

Stacking size

11 mm

Material

PA (Housing)

Gasket material

NBR

Media

dry compressed air, oiled or oil-free
neutral gases (5μm fi lter recommended)

Line connection

Flange MP13

Pneumatic
module

Type MP13 with thread M5, M7 or
Type MP13 with plug connector Ø 6 mm,
(Ø 4 mm, Ø ¼“ on request)

Manual actuation Yes (alternative versions without)
Rated power

0.3 W

Rated operating
mode

100 % continuous operation

Elec. connection
at the valve

rectangular plug RM 5.08 mm

Installation

with 2 screws M2 x 20

Orifi ce

4

QNn value air

300 l/min

Pressure range

0,3 W

Pressure range

2.5 ... 7 bar
1 ... 7 bar (with auxiliary control air)

Switching times

Opening: 35 ms
Closing: 45 ms