Burkert Type 1078-2 User Manual

Page 7

Advertising
background image

24

9.2. Adjustment of the 1078-1

DANGER

Risk of electric shock.

• To adjust the potentiometers, use an insulated

screwdriver.

The set operation mode starts when the device is
energized.

• Set the operation mode before energizing the

device combined with a solenoid valve.

To adjust the 1078-1:

Adjusting the valve operation mode.

Switches 4 and 5: To choose the
operating mode of the solenoid
valve

Switches 1, 2 and 3: To adjust the
range t

on

.

Switches 6, 7 and 8: To adjust the
range t

off

.

Potentiometer t

off

Potentiometer t

on

1

ON

2 34 5 6 7 8

1

3

1

3

Fig. 7: Adjustment elements of the 1078-1

English

25

The timer 1078-1 allows for controlling the ON (called t

on

) /

OFF (called t

off

) cycle of a solenoid valve.

Four operation modes can be set with switches 4 and 5.
See Fig. 7 and Fig. 8.

Switches 4
and 5

Operation mode of the solenoid valve

4

ON

5

ON (t

on

)/OFF (t

off

) cycle of the valve: Set the

time t

on

and the time t

off

T

on

T

off

4

ON

5

OFF (t

off

)/ON (t

on

) cycle of the valve: Set the

time t

on

and the time t

off

T

on

T

off

4

ON

5

Timed-out activation of the valve: Only set
the time t

on

T

on

T

off

4

ON

5

Delayed activation of the valve: Only set the
time delay t

off

T

on

T

off

Fig. 8: Operation modes of the 1078-1

Set the time range for t

on

with switches 1, 2 and 3 and/

or t

off

with switches 6, 7 and 8. See Fig. 7 and Fig. 9.

Switches 1, 2, 3 (

t

on

) and 6, 7, 8 (

t

off

)

Time range

1

ON

2 3

6 7 8

0,5-10 seconds

English

25

26

Switches 1, 2, 3 (

t

on

) and 6, 7, 8 (

t

off

)

Time range

1

ON

2 3

6 7 8

1,5-30 seconds

1

ON

2 3

6 7 8

5-100 seconds

1

ON

2 3

6 7 8

0,5-10 minutes

1

ON

2 3

6 7 8

1,5-30 minutes

1

ON

2 3

6 7 8

5-100 minutes

1

ON

2 3

6 7 8

12-240 minutes

1

ON

2 3

6 7 8

0,5-10 hours

Fig. 9: Time ranges for t

on

and t

off

English

27

Set the ON time t

on

with potentiometer t

on

and/or the

OFF time t

off

with potentiometer t

off

, with a flat screw-

driver of correct size. See Fig. 7 and Fig. 10.

1

3

Position 1 of the potenti-
ometer = minimum value
of the selected time range
(default position)

Position 3 of the poten-

tiometer = full scale of

the selected time range

min. value of the time
range + 10 % of the
time range

Cursor

min. value of the time range +
40 % of the time range

min. value of the time range +

50 % of the time range

min. value of the

time range +

80 % of the time

range

Fig. 10: Using the potentiometers of the 1078-1

English

27