The graph is used to determine the DN of the pipe and the
fitting appropriate to the application, according to the fluid
velocity and the flow rate.
Selection example:
• Specification: if the nominal flow is 10 m

3

/h, the dimen-

sioning of the optimal flow rate must be contained in 2
to 3 m/s

• Answer: on the chart, the intersection of flow rate and

flow velocity gives the appropriate diameter, DN40.

English

21

DN50
DN40
DN32
DN25

DN20

DN15

DN08

DN06

flow rate

Fluid velocity

0.1

0.3 0.5

1

3

5

10

0.01

0.02

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

m

3

/h

0.2

0.5

1

2

5

10

20

50

100

200

500

1000

2000

3000

l/min

0.3 0.5

1

3

5

10

30

m/s

fps

gpm

0.05

0.1

0.2

0.5

1

2

5

10

20

50

100

200

500

1000

English

21

22

Install the fitting on the pipe to comply with the
upstream and downstream distances defined by
standard EN ISO 5167-1 (see Fig. 3).

50 x DN 5 x DN

40 x DN 5 x DN

25 x DN 5 x DN

20 x DN 5 x DN

18 x DN 5 x DN

15 x DN 5 x DN

With control valve

Pipe with 2 elbows

at 90°

Pipe with 2 elbows at 90°

in 3 dimensions

Pipe with 1 elbow at 90°

or 1 T-piece

With pipe expansion

With pipe reduction

Fig. 3: Upstream and downstream distances depending

on the design of the pipes.

English

23

Use a flow conditioner, if necessary, to obtain the best
accuracy.

Prevent the formation of air bubbles in the pipe (see
Fig. 4).

Ensure the pipe is always filled with liquid (see Fig. 5).

Correct

Correct

Incorrect

Incorrect

Direction of fluid flow

Fig. 4: Additional recommendations on installation